Daikin FHYC35B7V1 [83/344] Kfido varies depending on discharge pipe temperature do when do dofini 45 c kfido kfidoh 128 128 hot start when do dofini 45 c kfido kfidol 179 128 cold start

Daikin CDX35JV1NB [83/344] Kfido varies depending on discharge pipe temperature do when do dofini 45 c kfido kfidoh 128 128 hot start when do dofini 45 c kfido kfidol 179 128 cold start
System control SiE18-201
72 Main Functions
Determination of initial frequency for cooling
Initial frequency FSR is determined based on the correction of outside air temperature (DOA)
and discharge pipe temperature (DO) in accordance with the above matrix.
FSR = KFIDO ° (2/128 ° (DOA - 35˚C) ° FINI1+FINI1)
KFIDO varies depending on discharge pipe temperature DO
When DO DOFINI (45˚C): KFIDO = KFIDOH (128/128) --- Hot start
When DO < DOFINI (45˚C): KFIDO = KFIDOL (179/128) --- Cold start
Reference Outside Air Temperature Hot Start Cold Start
35˚C 128/128 179/128
Outside Air
Temperature
Hot Start Cold Start
-5 37.5% 52.4%
0 45.3% 63.4%
5 53.1% 74.3%
10 60.9% 85.2%
15 68.8% 96.1%
20 76.6% 107.1%
25 84.4% 118.0%
30 92.2% 128.9%
35 100.0% 139.8%
40 107.8% 150.8%
45 115.6% 161.7%
Initial HZ multiplication
Hot start
Cold start
-10 -5 0 5 10 15 25 30 35 40 45 50
Outside
air temperature
0%
20%
40%
60%
80%
100%
120%
140%
160%
180%
(M1009)