Daikin FHYC35B7V1 — основные функции управления входным током в системах контроля [97/344]

Daikin FHYC60B7V1 [97/344] Outline
System control SiE18-201
86 Main Functions
3.16 Input Current Control
3.16.1 Input Current Control I
Outline The input current is detected by CT during compressor operation, and the input current value is
used to control the upper limit of the frequency.
As shown in the diagram below, the constraint frequency is varied differently in the stop,
drooping, no-change and reset zones.
When the constraint frequency remains in the stop zone for the specified period time, the
compressor is stopped.
The lower-limit current (input current droop value) in the drooping zone; I3 varies according to
the JIS mode or outside temperature (to stay within the system use area).
The input current control I is a higher-level constraint function that takes precedence over the
lower-limit control for 4-way valve operation guarantee.
Note Only 4-way valve operation guarantee has precedence, but not other lower-limit control.