AIR FILTER
1. Open the front panel.
Hold the panel at the recesses on the main unit (2
recesses on right and left sides) and lift it until it stops.
2. Pull out the air fi lters.
Push a little upwards the tab at the center of each air
lter, then pull it down.
3.Take off the Bio Filter with bacteriostatic, virustatic
functions.
Hold the recessed parts of the frame and unhook the
four claws.
4. Clean or replace each fi lter.
See fi gure.
When shaking off remaining water, do not wring the lter.
Recess on
main unit
5. Set the air fi lter and Bio Filter with bacteriostatic,
virustatic functions as they were and close the
front panel.
Insert claws of the fi lters into slots of the front panel.
Close the front panel slowly and push the panel at
the 3 points. (1 on each side and 1 in the middle.)
The air lter and Bio Filter with bacteriostatic,
virustatic functions have a symmetrical form in the
horizontal direction.
FRONT
Titanium Apatite Filter (Bio Filter)
Attached Concept
Air lter
Heat exchanger
Bio Filter attached part
Titanium Apatite Filter
Filter frame
Tab
Air filter
Bio Filter with
bacteriostatic,
virustatic functions
* Bio Filter and Titanium Apatite Filter are optional accessories.
Bio filter packs in a
hermetically-sealed bag.
Take it out
at the time of installation.
Slip the filter in between filter frame and
Titanium Apatite Filter.
Titanium Apatite Filter
Bio Filter
Filter frame
Installation Procedure for Bio Filter
CAUTION
Please use this Bio Filter during dry season such as winter.
Storage, handling and disposal methods.
The lifetime of this Bio Filter is about a year after opening.
IIn case you do not use this Bio Filter right away, please don’t place the Bio Filter in any place where it will be
subjected to direct sunlight, high temperatures and/or high humidity.
There can be slight differences between Bio Filter color because of the manufacturing reasons, there is no effect
on the unit performance.
PPlease open this bag right before you use it. Bio Filter should remain unopened and sealed in its packaging until
right before usage. (It may cause performance deterioration or quality change.)
To avoid danger of suffocation and any unexpected accident, please dispose the plastic bag immediately after you
remove the Bio Filter. Keep out of reach of babies and children.
IIf you keep this Bio Filter for a long time, please keep it unopened and store in a cool place avoiding direct
sunlight.
Please dispose the old Bio Filter as nonfl ammable garbage after use.
Operation with dirty fi lters:
(1) cannot deodorize the air. (3) results in poor heating or cooling.
(2) cannot clean the air. (4) may cause odour.
To order Bio Filter, contact the service shop where you bought the air conditioner.