List of contents
Operating instructions
2
Daikin RoCon HP
Daikin Control
008.1420844 – 05/2014
1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Observing instructions . . . . . . . . . . . . . . . . . . . . 3
1.2 Warning signs and explanation of symbols . . . . 3
1.3 Avoid danger . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Proper use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Product description. . . . . . . . . . . . . . . . . . . 5
3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.2.1 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3.2.2 Operating elements. . . . . . . . . . . . . . . . . . . . . . . . .7
3.3 Operating concept . . . . . . . . . . . . . . . . . . . . . . . 8
3.4 Basic functions and operating modes . . . . . . . . 9
3.4.1 System information (Info) . . . . . . . . . . . . . . . . . . . .9
3.4.2 Setting the operating mode . . . . . . . . . . . . . . . . . .11
3.4.3 Temperature setting Daytime room temperature .12
3.4.4 Temperature setting Economy mode . . . . . . . . . .12
3.4.5 Temperature setting hot water generation . . . . . .13
3.4.6 Unplanned hot water generation . . . . . . . . . . . . . .13
3.4.7 Switching time program. . . . . . . . . . . . . . . . . . . . .13
3.4.8 System settings. . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.4.9 Terminal function. . . . . . . . . . . . . . . . . . . . . . . . . .15
3.4.10 Quite Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
3.4.11 SMART GRID . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
3.5 Special functions . . . . . . . . . . . . . . . . . . . . . . . 17
3.5.1 Manual Operation . . . . . . . . . . . . . . . . . . . . . . . . .17
3.6 Special system settings . . . . . . . . . . . . . . . . . . 18
3.6.1 Access Rights (Technician password) . . . . . . . . .18
3.6.2 Heat curve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
3.6.3 Cooling characteristic curve . . . . . . . . . . . . . . . . .19
3.6.4 Weather-controlled flow temperature regulation . .20
3.6.5 Frost protection function . . . . . . . . . . . . . . . . . . . .20
3.6.6 Interlink function . . . . . . . . . . . . . . . . . . . . . . . . . .21
3.6.7 Additional heat generator . . . . . . . . . . . . . . . . . . .21
3.6.8 Heating support. . . . . . . . . . . . . . . . . . . . . . . . . . .22
3.6.9 Special function: Switching contacts . . . . . . . . . . .22
3.6.10 Air Purge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
3.6.11 Legionella protection . . . . . . . . . . . . . . . . . . . . . . .23
3.6.12 Reset to factory settings (Reset). . . . . . . . . . . . . .24
3.6.13 Screed Program . . . . . . . . . . . . . . . . . . . . . . . . . .25
3.6.14 Relay Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
3.6.15 Settings for optional circulation pump . . . . . . . . . .27
3.6.16 Remote control via Internet . . . . . . . . . . . . . . . . . .27
4 Initial start-up. . . . . . . . . . . . . . . . . . . . . . . 28
4.1 Starting up the Daikin Altherma EHS(X/H). . . . 28
4.2 Connect the optional RoCon devices and
start them up . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.2.1 Starting up the EHS157068 mixer module . . . . . .28
4.2.2 Starting up the EHS157034 room station . . . . . . .29
4.2.3 Caretaker function. . . . . . . . . . . . . . . . . . . . . . . . .30
5 Parameter settings . . . . . . . . . . . . . . . . . . .31
5.1 Explanation of the parameter tables . . . . . . . . 31
5.2 Rotary switch setting: Configuration . . . . . . . . 31
5.2.1 Level "Setup". . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.2.2 Level "System Configuration" . . . . . . . . . . . . . . . 34
5.2.3 Level "HC Configuration". . . . . . . . . . . . . . . . . . . 35
5.2.4 Level "DHW Configuration" . . . . . . . . . . . . . . . . . 37
5.3 Rotary switch setting: DHW Install . . . . . . . . . 37
5.4 Rotary switch setting: Operating Mode . . . . . 37
5.5 Rotary switch setting: Set Temp Day . . . . . . . 38
5.6 Rotary switch setting: Set Temp Night . . . . . . 38
5.7 Rotary switch setting: DHW Set Temp . . . . . . 38
5.8 Rotary switch setting: Time Program . . . . . . . 39
5.9 Rotary switch setting: Remote Param . . . . . . 39
5.10 Rotary switch setting: Info . . . . . . . . . . . . . . . 40
5.11 Exit button: Sonderfunktion . . . . . . . . . . . . . . . 41
5.12 Parameter level "Basic Configuration" . . . . . . 41
5.13 Parameter levels for the EHS157068 mixer
module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.13.1 Rotary switch setting: Configuration,
level "Setup" . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.13.2 Rotary switch setting: Configuration,
level "Mixer Config" . . . . . . . . . . . . . . . . . . . . . . . 43
6 Errors, malfunctions and messages . . . . .45
6.1 Recognising errors, correcting malfunctions . . 45
6.1.1 Current fault display . . . . . . . . . . . . . . . . . . . . . . 45
6.1.2 Read Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.1.3 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.2 Emergency operation . . . . . . . . . . . . . . . . . . . 46
6.3 Malfunctions and fault codes. . . . . . . . . . . . . . 46
7 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
8 Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
8.1 User-specific settings . . . . . . . . . . . . . . . . . . . 48
8.1.1 Switching time program. . . . . . . . . . . . . . . . . . . . 48
8.2 Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
8.2.1 Data bus addresses . . . . . . . . . . . . . . . . . . . . . . 49
8.3 Other items . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
9 List of keywords . . . . . . . . . . . . . . . . . . . . .51
Содержание
- Operating instructions p.1
- Daikin control rocon hp ehs157034 ehs157068 p.1
- Special system settings 18 p.2
- Parameter 49 p.2
- Connect the optional rocon devices and start them up 28 p.2
- Special functions 17 p.2
- Other items 50 p.2
- Basic functions and operating modes 9 p.2
- Operation 6 p.2
- Avoid danger 3 p.2
- Safety 3 p.2
- Operating concept 8 p.2
- Rotary switch setting time program 39 p.2
- Observing instructions 3 p.2
- Rotary switch setting set temp night 38 p.2
- Notes 8 p.2
- Rotary switch setting set temp day 38 p.2
- Module 42 p.2
- Rotary switch setting remote param 39 p.2
- Malfunctions and fault codes 46 p.2
- Rotary switch setting operating mode 37 p.2
- Rotary switch setting info 40 5 1 exit button sonderfunktion 41 5 2 parameter level basic configuration 41 5 3 parameter levels for the ehs157068 mixer p.2
- List of keywords 1 p.2
- Rotary switch setting dhw set temp 38 p.2
- List of contents p.2
- Rotary switch setting dhw install 37 p.2
- Initial start up 28 p.2
- Rotary switch setting configuration 31 p.2
- Glossary 7 p.2
- Recognising errors correcting malfunctions 45 p.2
- General 6 p.2
- Warning signs and explanation of symbols 3 p.2
- Proper use 4 p.2
- Explanation of the parameter tables 31 p.2
- User specific settings 48 p.2
- Product description 5 p.2
- Errors malfunctions and messages 5 p.2
- Starting up the daikin altherma ehs x h 28 p.2
- Parameter settings 1 p.2
- Emergency operation 46 p.2
- X safety p.3
- Warning signs and explanation of symbols p.3
- Validity p.3
- Special warning signs p.3
- Safety p.3
- Relevant documents p.3
- Observing instructions p.3
- Meaning of the warnings p.3
- Handling instructions p.3
- Display readouts of the rocon control p.3
- Avoid danger p.3
- X safety p.4
- Proper use p.4
- X product description p.5
- Product description p.5
- X operation p.6
- Operation p.6
- Maximum energy utilisation p.6
- General p.6
- Explanation of symbols p.6
- Display and operating elements p.6
- Display p.6
- X operation p.7
- Rotary switch p.7
- Operating elements p.7
- X operation p.8
- Operating concept p.8
- Exit button p.8
- Button block p.8
- X operation p.9
- System information info p.9
- Display operating data p.9
- Basic functions and operating modes p.9
- Automatic defrosting function p.9
- X operation p.10
- Displaying the water pressure p.10
- X operation p.11
- Setting the operating mode p.11
- Operating modes heating cooling p.11
- Operating mode summer p.11
- Operating mode standby stand by p.11
- Operating mode reducing p.11
- Operating mode automatic 1 timer programme p.11
- Temperature setting daytime room temperature p.12
- Operating mode automatic 2 timer programme p.12
- X operation p.12
- Temperature setting economy mode p.12
- X operation p.13
- Unplanned hot water generation p.13
- Temperature setting hot water generation p.13
- Switching time program p.13
- Permanent timer programmes p.13
- Adjustment p.13
- X operation p.14
- X operation p.15
- Terminal function p.15
- Temporary timer programmes p.15
- System settings p.15
- Setting the language date time p.15
- Assign the terminal address of the daikin altherma ehs x h to the control element rocon b1 p.16
- Activating deactivating normal operation p.16
- X operation p.16
- Smart grid p.16
- Quite mode p.16
- X operation p.17
- Special functions p.17
- Manual operation p.17
- X operation p.18
- Special system settings p.18
- Manually adapting the heating curve p.18
- Heat curve p.18
- Expert p.18
- Caution danger of overheating with underfloor heating p.18
- Access rights technician password p.18
- X operation p.19
- Cooling characteristic curve p.19
- Caution risk of condensation p.19
- X operation p.20
- Weather controlled flow temperature regulation p.20
- If a mixer module is connected p.20
- Frost protection function p.20
- X operation p.21
- Interlink function p.21
- Caution p.21
- Additional heat generator p.21
- X operation p.22
- Special function switching contacts p.22
- Heating support p.22
- Electrical connections to settings 2 and 3 of the parameter function heating rod p.22
- Caution p.22
- X operation p.23
- Legionella protection p.23
- Air purge p.23
- X operation p.24
- Reset to factory settings reset p.24
- Possibility 3 p.24
- Possibility 2 p.24
- Option 1 p.24
- X operation p.25
- Screed program p.25
- Ready to apply heating p.25
- Function heating p.25
- X operation p.26
- Screed program setting and starting p.26
- X operation p.27
- Settings for optional circulation pump p.27
- Setting the timer programme for the circulation pump p.27
- Remote control via internet p.27
- Relay test p.27
- X initial start up p.28
- Starting up the ehs157068 mixer module p.28
- Starting up the daikin altherma ehs x h p.28
- Initial start up p.28
- Connect the optional rocon devices and start them up p.28
- X initial start up p.29
- Starting up the ehs157034 room station p.29
- Procedure for commissioning p.29
- A configuration for setting living room p.29
- X initial start up p.30
- Caretaker function p.30
- B configuration for setting mixing valve p.30
- Rotary switch setting configuration p.31
- Parameter settings p.31
- Level setup p.31
- Explanation of the parameter tables p.31
- X parameter settings p.31
- X parameter settings p.32
- X parameter settings p.33
- Tab 5 1 parameter in rotary switch setting configuration level setup p.33
- X parameter settings p.34
- Level system configuration p.34
- X parameter settings p.35
- Tab 5 2 parameter in rotary switch setting configuration level system configuration p.35
- Level hc configuration p.35
- Depending on the version of the device software certain information parameters for the device not described in tab 5 2 can be displayed at this level for this see tab 5 12 p.35
- X parameter settings p.36
- Tab 5 3 parameter in rotary switch setting configuration level hc configuration p.36
- X parameter settings p.37
- Rotary switch setting operating mode p.37
- Rotary switch setting dhw install p.37
- Level dhw configuration p.37
- X parameter settings p.38
- Tab 5 9 parameter in rotary switch setting dhw set temp p.38
- Tab 5 8 parameter in rotary switch setting set temp night p.38
- Tab 5 7 parameter in rotary switch setting set temp day p.38
- Rotary switch setting set temp night p.38
- Rotary switch setting set temp day p.38
- Rotary switch setting dhw set temp p.38
- X parameter settings p.39
- Tab 5 11 parameter in rotary switch setting remote param p.39
- Tab 5 10 parameter in rotary switch setting time program p.39
- Rotary switch setting time program p.39
- Rotary switch setting remote param p.39
- X parameter settings p.40
- Tab 5 12 parameter in rotary switch setting info p.40
- Rotary switch setting info p.40
- After in the rotary switch position configuration level setup the parameter system config has been set to inac tive or delete p.41
- X parameter settings p.41
- This parameter level appears only if at initial commissioning if the query use standard configura tion is answered by no or p.41
- Tab 5 14 parameter in the level basic configuration p.41
- Tab 5 13 parameter in the level sonderfunktion p.41
- Parameter level basic configuration p.41
- Exit button sonderfunktion p.41
- Rotary switch setting info p.42
- Rotary switch setting dhw set temp p.42
- Rotary switch setting dhw install p.42
- Rotary switch setting configuration level setup p.42
- Rotary switch setting configuration p.42
- X parameter settings p.42
- Parameter levels for the ehs157068 mixer module p.42
- When the assigned control unit is set to living room the t room adj parameter is available the rotary switch can be used to change the room target temperature to the range 5 k to 5 k this function is not available if the control unit is being used as a terminal function for remote control p.42
- No function p.42
- The parameter levels parameter priorities setting ranges and associated functions are essentially the same as those described in the preceding sections p.42
- The description below relates only to the sections indicated areas where there are significant differences are described in greater detail p.42
- Level setup p.42
- See sections 5 3 and 5 3 p.42
- In some cases there exist at individual levels a restricted scope of available parameters p.42
- See section 5 0 p.42
- If the assigned control unit is set to mix valve x the displayed values relate to the assigned heating circuit and to the compo nents connected to the ehs157068 pump mixer valve p.42
- See section 5 p.42
- Rotary switch setting time program p.42
- Rotary switch setting set temp night p.42
- Rotary switch setting set temp day p.42
- Rotary switch setting remote param p.42
- Rotary switch setting operating mode p.42
- X parameter settings p.43
- Rotary switch setting configuration level mixer config p.43
- Rotary switch setting configuration p.43
- Level mixer config p.43
- X parameter settings p.44
- Tab 5 16 parameter in rotary switch setting configuration level mixer config p.44
- X errors malfunctions and messages p.45
- Troubleshooting p.45
- Recognising errors correcting malfunctions p.45
- Read protocol p.45
- Errors malfunctions and messages p.45
- Current fault display p.45
- X errors malfunctions and messages p.46
- Malfunctions and fault codes p.46
- Emergency operation p.46
- X glossary p.47
- Glossary p.47
- X notes p.48
- User specific settings p.48
- Switching time program p.48
- X notes p.49
- Rocon appliance data bus address comments p.49
- Parameter p.49
- Enter your parameter changes in the table below p.49
- Data bus addresses p.49
- Circulation time p.49
- X notes p.50
- Other items p.50
- X list of keywords p.51
- List of keywords p.51
Похожие устройства
-
Daikin EVLQ08CAV3Руководство по применению для установщика -
Daikin EVLQ08CAV3Справочное руководство для монтажника -
Daikin EVLQ08CAV3Общие правила техники безопасности -
Daikin EVLQ08CAV3Инструкция по монтажу -
Daikin EVLQ05CAV3Справочное руководство для монтажника -
Daikin EVLQ05CAV3Руководство по применению для установщика -
Daikin EVLQ05CAV3Общие правила техники безопасности -
Daikin EVLQ05CAV3Инструкция по монтажу -
Daikin EHYKOMB33AA3Справочное руководство для монтажника -
Daikin EHYKOMB33AA3Руководство по применению для установщика -
Daikin EHYKOMB33AA3Руководство по эксплуатации -
Daikin EHYKOMB33AA2Руководство по применению для установщика
Подробное руководство по эксплуатации и настройке систем управления. Узнайте о функциях, режимах работы и мерах безопасности для эффективного использования.