Daikin EHSHB08P50A — инструкции по эксплуатации для систем отопления и горячего водоснабжения [32/52]

Daikin EHSHB04P30A [32/52] X parameter settings
Operating instructions
32
Daikin RoCon HP
Daikin Control
008.1420844 – 05/2014
5 x Parameter settings
Function Heating
Rod
Setting as to whether there is an additional heat generator (WEZ) for hot water genera-
tion and heating support (see chapter 3.6.7).
0: No additional WEZ
1: Optional backup heater
2: Alternative WEZ takes over the hot water generation and heating support
3: Alternative WEZ 1 takes over hot water generation and alternative WEZ 2 takes over
h
eating support
N E 0 - 3 1 1
HZU Heating support from domestic hot water storage tanks when the minimum temperature
i
s exceeded (see chapter 3.6.8 and parameter [TDiff-DHW CH Support]).
Off: No heating support
On: Heating support function active
N E Off
On
On -
Equilibrium Func. The bivalence function is relevant for operati
on of the optional ancillary heater based on
a backup demand (room heating operation).
Off: Operation of the backup heater is always possible.
On: The backup heater is only enabled if th
e temperature falls below the one set in the
parameter [Equilibrium Temp].
N E Off
On
On -
SMART GRID Evaluation of the SG signal (see chapter 3.4.11).
0: SMART GRID function not active; SG signal not evaluated.
1: Depending on the signal from the energy sup
ply company, the heat pump is turned off
(no frost-protection function - see chapter 3.6.5) or run in high-temperature mode.
N E 0 - 1 0 -
Mode SG Only if parameter [SMART GRID] = 1:
Used for a possible target temperature increase in the case of a SMART GRID start com-
mand.
0: Comfort (5 K increase in target domestic hot water temperature)
1: Standard (2 K increase in inflow target temperature and 5 K increase in target domes-
tic hot water temperature)
2: Eco (5 K increase in inflow target temperature and 7 K increase in target domestic hot
wa
ter temperature)
N E 0 - 2 1 1
HT/NT Function Setting which specifies which heat sources are switched off when the standard signal is
r
eceived from the energy supply company (EVU) in the case of the customer having an
off-peak tariff network connection.
0: Deactivated (no effect)
1: Refrigerant compressor switched off
2: Refrigerant compressor and reserve heating switched off
3: Everything switched off (no f
rost protection - see chapter 3.6.5)
N E 0 - 3 0 1
HT/NT Contact Specifies whether the HT/NT input is an NC or NO contact.
0: NO contact (switching contact closed =
standard tariff)
1: NC contact (switching contact closed = off-peak tariff)
N E 0 - 1 0 -
Room thermostat Configuration of a room thermostat connected to the port J16 on the Daikin Altherma
E
HS(X/H) using potential-free contacts.
Off: Deactivated
On: (Only when parameter [Interlink fct] = Off)
Evaluation of
heating and cooling switching contacts at plug connection J16
on the RoCon BM1 circuit board (only when none of the operating modes "Standby",
"
Economy mode", "Summer", "Vacation", "Holiday" or "Screed" is active):
a) Closed switching contact
heating: Operating mode is switched to "Heating".
Priority if both switching contacts are closed.
b) Closed switching contact
cooling: Operating mode is switched to "Cooling".
c) Open contacts: Only frost
protection active.
N E Off
On
Off -
Interlink fct Configuration for systems operating with 2 different inflow target temperatures
(s
ee chapter 3.6.6).
A possible use for this might be the additional integration of aFWXV(15/20)AVEB in a
sur
face heating and cooling system.
Requirement: 2 room thermostats need to be connected to plug connection J16 on the
Daikin Altherma EHS(X/H).
Off: Deactivated
On: Evaluation of and cooling switching contacts at plug connection J16 on
the RoCon BM1 circuit board.
Activation of cooling mode only possible by changing operating mode to "Cooling"
(s
ee chapter 3.4.2).
Setting for the parameter [Room thermostat] no longer evaluated.
a) Open switching contacts: Only frost protection active.
b) Operating modes "Heating" and "Automatic 1" / "Automatic 2" active during
switchi
ng cycles in day mode.
Closed switching contact heating
= IL1:
The
system operates according to the normal infeed target temperature accord-
ing to the parameter settings in "HC C
onfiguration" > "Heating".
Closed switching contact cooling
= IL2:
The syste
m operates according to the increased inflow target temperature (nor-
mal inflow target temperature + value of parameter [T-Flow CH adj]. Priority if
bot
h switching contacts are closed.
c) "Cooling" operating mode active.
Closed switching contact heating
= IL1:
The
system operates according to the normal infeed target temperature accord-
ing to the parameter settings in "HC C
onfiguration" > "Cooling".
Closed switching contact cooling
= IL2:
The syst
em operates according to the reduced inflow target temperature (nor-
mal inflow target temperature - value of parameter [T-Flow Cooling adj]. Priority
if b
oth switching contacts are closed.
N E Off
On
Off
-
Sub-
level
Parameter Description Access Setting range
Min / Max
Factory
setting
Increment
BE HF