Installation and maintenance manual
22
Daikin Altherma EHS(X/H)
Daikin Solar tank with integrated interior heat pump unit
008.1420744 – 06/2015
3 x Set-up and installation
● Connect the exterior temperature sensor to a twin-core
sensor line (minimum diameter 1
mm
2
).
● Install the sensor line to the Daikin Altherma EHS(X/H).
● Connect the sensor line to the plug connection J8 on the
board RoCon BM1 (see fig. 3-23).
Fig. 3-23 Connection of the exterior temperature sensor RoCon OT1 to
the Daikin Altherma EHS(X/H) (operating as a single solution
or master in a data bus)
After connecting the exterior temperature sensor RoCon OT1 to
the regulator RoCon HP of the Daikin Altherma EHS(X/H), the
parameter [Outside Config] must be set to "On".
3.4.12 Connection of an external switching contact
By connecting an external switching contact (fig. 3-24) the oper-
ating mode of the Daikin Altherma
EHS(X/H) can be changed.
The current operating mode can be switched thanks to a
cha
nging resistance reading (tab. 3-1). Changing the operating
mode is only effective as long as the external switching contact is
clo
sed.
The operating mode has an effect on the direct circuit of the
Daikin Altherma EHS(X/H), and on all other heating circuits that
can be optionally connected to this device.
The operating mode shown in the controller display can deviate
from the operating mode activated in the rotary switch setting
.
An operating mode activated by an external switch contact is
shown on the controller by "EXT.", followed by the symbol of the
operating mode (see operating instructions for the controller).
If special functions, such as "Manual Operation" are activated,
the
input is not evaluated.
Fig. 3-24 Connection of the EXT switching contact
Operating mode Resistance R
V
Tolerance
Standby < 680 Ω
± 5 %
Heating 1200 Ω
Reducing 1800 Ω
Summer 2700 Ω
Automatic 1 4700 Ω
Automatic 2 8200 Ω
Tab. 3-1 Resistance values for the evaluation of the EXT signal
When the resistance readings are greater than the
value for "Automatic 2", the input will be ignored.
NOTE REGARDING THE CONNECTION OF A
DAIKIN SOLAR SYSTEM
By means of the function [HZU] integrated into the
RoCon HP integrated [HZU] control unit
(see operating manual for the control unit) it is not nec-
essary to connect the EXT connection with the con-
nection of the burner blocking contact of the Daikin
s
olar system.
3.4.13 External demand signal (EDS)
By connecting the EDS switch contact to the Daikin Altherma
EHS(X/H) (fig. 3-25) and through the corresponding parameteri-
sation in its RoCon HP control unit, a heating demand can be
generated via an external switch contact. If the switch contact is
closed, the Daikin Altherma EHS(X/H) switches to the heating
mode. The flow temperature is adjusted to the temperature that
is set in the parameters [T-Flow Day].
The EDS switching contact has preference of a request via the
ro
om thermostat.
In Cooling, Stand-by, Manual and Summer mode, the switching
contact is not evaluated. In addition, the heating limits are not
taken into consideration.
Fig. 3-25 Connection EBA switch contact
Содержание
- Indoor unit for air water heat pumps daikin altherma integrated solar unit p.1
- Installation and maintenance manual p.1
- Malfunctions 43 p.3
- Tightening torque 63 p.3
- Emergency operation 54 p.3
- Temporary shutdown 35 p.3
- List of keywords 67 p.3
- Electrical connection 7 p.3
- Technical data 58 p.3
- List of contents p.3
- Dimensions and connections 3 p.3
- Start up 31 p.3
- Laying coolant lines 29 p.3
- Design and components p.3
- Set up and installation 13 p.3
- Intended use p.3
- Decommissioning 35 p.3
- Set up 5 p.3
- Instructions for operating safety p.3
- Circuit diagram daikin altherma ehs x h 64 p.3
- Service and maintenance 38 p.3
- Initial commissioning 31 p.3
- Characteristic lines 61 p.3
- Safety 4 p.3
- Hydraulic system connection 55 p.3
- Avoid danger p.3
- Removing the protective cover 38 p.3
- General 38 p.3
- Activities to be performed annually 38 p.3
- Recognising errors correcting malfunctions 42 p.3
- Final shutdown 37 p.3
- Filling the system with water 30 p.3
- Re commissioning 33 p.3
- Filling and topping up the storage tank 40 p.3
- Product description 7 p.3
- Filling and topping up the heating system 41 p.3
- Pressure test and filling the coolant circuit 30 p.3
- Fault codes 47 p.3
- Observing instructions p.3
- Errors malfunctions and messages 42 p.3
- Water connection 6 p.3
- Notes 65 p.3
- Warning signs and explanation of symbols p.3
- Monitoring and configuration dip switch 53 p.3
- Equipment data 58 p.3
- X safety p.4
- Warning signs and explanation of symbols p.4
- Validity p.4
- Special warning signs p.4
- Safety p.4
- Relevant documents p.4
- Observing instructions p.4
- Meaning of the warnings p.4
- Handling instructions p.4
- Intended use p.5
- Instructions for operating safety p.5
- Electrical installation p.5
- Before working on the hydraulic system p.5
- Avoid danger p.5
- X safety p.5
- X safety p.6
- Working on cooling systems heat pump p.6
- Site of installation p.6
- Requirements for the heating water p.6
- Operation p.6
- Instructing the user owner p.6
- Heating system and sanitary connection p.6
- X product description p.7
- Top of unit p.7
- Product description p.7
- Design and components p.7
- X product description p.8
- Fig 2 2 design and components of the daikin altherma ehs x h p30a external view and internal design for legend descriptions see tab 2 1 p.8
- Device external and internal design daikin altherma ehs x h p30a p.8
- Device external and internal design daikin altherma ehs x h b p30a p.9
- X product description p.9
- Fig 2 3 design and components of the daikin altherma ehs x h b p30a external view and internal design for legend descriptions see tab 2 1 p.9
- X product description p.10
- Fig 2 4 design and components of the daikin altherma ehs x h p50a external view and internal design for legend descriptions see tab 2 1 p.10
- Device external and internal design daikin altherma ehs x h p50a p.10
- X product description p.11
- Fig 2 5 design and components of the daikin altherma ehs x h b p50a external view and internal design for legend descriptions see tab 2 1 p.11
- Device external and internal design daikin altherma ehs x h b p50a p.11
- X product description p.12
- X set up and installation p.13
- Set up and installation p.13
- Dimensions and connections p.13
- Daikin altherma ehs x h p30a p.13
- Daikin altherma ehs x h p50a p.14
- X set up and installation p.14
- Scope of delivery p.15
- X set up and installation p.15
- Set up p.15
- X set up and installation p.16
- Water connection p.16
- X set up and installation p.17
- Electrical connection p.17
- Connecting hydraulic lines p.17
- X set up and installation p.18
- Overall connection plan daikin altherma ehs x h p.18
- Fig 3 7 overall connection diagram for electrical connection during device installation p.18
- Explanation of symbols and abbreviations in this chap ter see tab 3 2 and tab 3 3 p.18
- The a1p circuit board comes pre connected to the unit no as sembly or connection work is necessary on the a1p circuit board p.19
- Terminal assignment for the rtx ehs circuit board p.19
- Terminal assignment for the rtx al4 circuit board p.19
- Position of the circuit boards p.19
- Connection assignment circuit board a1p p.19
- X set up and installation p.19
- X set up and installation p.20
- Removing the protective cover p.20
- Mains connection daikin altherma ehs x h p.20
- Connection assignment circuit board rocon bm1 p.20
- X set up and installation p.21
- Opening the control housing and establishing electrical connections p.21
- Connection of external temperature sensor rocon ot1 p.21
- Connection of erlq exterior heat pump unit p.21
- X set up and installation p.22
- External demand signal eds p.22
- Connection of an external switching contact p.22
- Connection variant 2 p.23
- Connection variant 1 p.23
- Connection of the electrical daikin backup heater ekbuxx p.23
- Connection of an external heat generator p.23
- X set up and installation p.23
- X set up and installation p.24
- Caution p.24
- X set up and installation p.25
- Daikin room station ehs157034 p.25
- Daikin mixer module ehs157068 p.25
- Connection optional daikin rocon system components p.25
- Connection of the daikin room thermostat p.25
- X set up and installation p.26
- Low tariff mains connection ht nt p.26
- Internet gateway daikin ehs157056 p.26
- Connection switch contacts aux outputs p.26
- Connection of the daikin fwxv 15 20 aveb p.26
- C onnection of the daikin fwxv 15 20 aveb p.26
- Symbols and legend keys on connection and circuit diagrams p.27
- Connection intelligent controller smart grid sg p.27
- X set up and installation p.27
- X set up and installation p.28
- X set up and installation p.29
- Laying coolant lines p.29
- X set up and installation p.30
- Pressure test and filling the coolant circuit p.30
- Filling the system with water p.30
- Filling the storage tank p.30
- Filling the hot water heat exchanger p.30
- Filling the heating system p.30
- Checking the water quality and adjusting the pressure gauge p.30
- Start up p.31
- Set the commissioning parameters p.31
- Requirements p.31
- L commissioning p.31
- Initial commissioning p.31
- X start up p.31
- X start up p.32
- Venting the internal heating circulation pump p.32
- Expert p.32
- X start up p.33
- Start up p.33
- Requirements p.33
- Re commissioning p.33
- Configuring screed program parameters only if necessary p.33
- Check minimum flow p.33
- Activating the parameter air purge p.33
- X start up p.34
- Without solar installation p.35
- Temporary shutdown p.35
- Draining the storage tank p.35
- Decommissioning p.35
- X decommissioning p.35
- X decommissioning p.36
- Only for the solar installation p.36
- Draining the heating circuit and hot water circuit p.36
- X decommissioning p.37
- Recommendations for disposal p.37
- Final shutdown p.37
- X service and maintenance p.38
- Service and maintenance p.38
- Removing the protective cover p.38
- Legal requirements p.38
- General p.38
- Activities to be performed annually p.38
- X service and maintenance p.39
- With kfe filling connection or with installed solar system see also chapter 5 p.40
- Filling and topping up the storage tank p.40
- X service and maintenance p.40
- Without installed solar system p.40
- X service and maintenance p.41
- Filling and topping up the heating system p.41
- X errors malfunctions and messages p.42
- Troubleshooting p.42
- Recognising errors correcting malfunctions p.42
- Read protocol p.42
- Errors malfunctions and messages p.42
- Current fault display p.42
- X errors malfunctions and messages p.43
- Malfunctions p.43
- X errors malfunctions and messages p.44
- X errors malfunctions and messages p.45
- X errors malfunctions and messages p.46
- Fault codes p.47
- X errors malfunctions and messages p.47
- X errors malfunctions and messages p.48
- X errors malfunctions and messages p.49
- X errors malfunctions and messages p.50
- X errors malfunctions and messages p.51
- X errors malfunctions and messages p.52
- Touching live parts can result in an electric shock and lead to potentially fatal injuries and burns p.53
- Pump continuous running off p.53
- No designation factory setting p.53
- Monitoring and configuration dip switch p.53
- Domestic hot water gener ation on p.53
- Do not change off p.53
- Disconnect the system from the power supply open the control housing and remove the rocon bm1 board see chapter 3 check the dip switch setting on the a1p circuit board of the daikin altherma ehs x h adjust where necessary see tab 7 4 the factory preset may only be changed if e g an optional accessory was connected replace the rocon bm1 switch board close the control housing and reconnect the power supply p.53
- Dip switch settings are not recognised until a brief inter ruption to the power supply p.53
- Dip switch p.53
- Before beginning work on live parts disconnect all of the systems circuits from the power supply switch off main switch disconnect fuse and secure against unintentional restart p.53
- X errors malfunctions and messages p.53
- Warning p.53
- X errors malfunctions and messages p.54
- Emergency operation p.54
- X hydraulic system connection p.55
- Hydraulic system connection p.55
- X hydraulic system connection p.56
- X hydraulic system connection p.57
- X technical data p.58
- Technical data p.58
- Equipment data p.58
- Daikin altherma ehs x h p30a p.58
- X technical data p.59
- X technical data p.60
- Daikin altherma ehs x h p50a p.60
- Characteristic lines p.61
- X technical data p.61
- Sensor characteristic lines p.61
- X technical data p.62
- Sensor resistance in ohm p.62
- Sensor output frequency in hz p.62
- Pt 1000 p.62
- Measured temperature in c p.62
- Measured flow in l min p.62
- M l min p.62
- Fls sensor flow temperature p.62
- 14 229 hz p.62
- X technical data p.63
- Tightening torque p.63
- Characteristic curves for pumps p.63
- Fig 9 8 circuit diagram daikin altherma ehs x h for legend see tab 3 3 p.64
- Circuit diagram daikin altherma ehs x h p.64
- X technical data p.64
- X notes p.65
- X notes p.66
- X list of keywords p.67
- Numerics p.67
- List of keywords p.67
Похожие устройства
-
Daikin EVLQ08CAV3Руководство по применению для установщика -
Daikin EVLQ08CAV3Справочное руководство для монтажника -
Daikin EVLQ08CAV3Общие правила техники безопасности -
Daikin EVLQ08CAV3Инструкция по монтажу -
Daikin EVLQ05CAV3Справочное руководство для монтажника -
Daikin EVLQ05CAV3Руководство по применению для установщика -
Daikin EVLQ05CAV3Общие правила техники безопасности -
Daikin EVLQ05CAV3Инструкция по монтажу -
Daikin EHYKOMB33AA3Справочное руководство для монтажника -
Daikin EHYKOMB33AA3Руководство по применению для установщика -
Daikin EHYKOMB33AA3Руководство по эксплуатации -
Daikin EHYKOMB33AA2Руководство по применению для установщика
Подробное руководство по установке и обслуживанию системы отопления с интегрированным тепловым насосом. Узнайте, как правильно подключить датчики и управлять режимами работы.