Daikin RRLQ011CAW1 — установка и подключение электрической проводки для систем отопления [40/116]

Daikin RRLQ011CAW1 [40/116] To connect the electrical wiring on the outdoor unit
7 Installation
Installer reference guide
40
RRLQ011~016CA + RHBH/X11+16CB
ROTEX HPSU low temperature Bi‑bloc
4P384980-1B – 2016.03
Wire type Installation method
Single core wire
cb
c
aa
A
AA´
a Curled single core wire
b Screw
c Flat washer
Stranded conductor
wire with round
crimp-style terminal
c b ba c
a
B
B
a Terminal
b Screw
c Flat washer
Tightening torques
Item Tightening torque (N•m)
M4 (X1M) 1.2~1.8
M5 (X1M) 2.0~3.0
M5 (earth) 3.0~4.0
7.9.5 Specifications of standard wiring
components
Component RRLQ_V3 RRLQ_W1
Power supply
cable
MCA
(a)
34.2A 16.3A
Voltage 230V 400V
Phase 1~ 3N~
Frequency 50Hz
Wire sizes Must comply with applicable
legislation
Interconnection cable Minimum cable section of
2.5mm² and applicable for
230V
Recommended field fuse 40A 20A
Earth leakage circuit breaker Must comply with applicable
legislation
(a) MCA=Minimum circuit ampacity. Stated values are
maximum values (see electrical data of combination with
indoor units for exact values).
7.9.6 To connect the electrical wiring on the
outdoor unit
NOTICE
Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1 Remove the service cover. See "7.2.2 To open the outdoor
unit"on page29.
2 Strip insulation (20mm) from the wires.
a b
a Strip wire end to this point
b Excessive strip length may cause electrical shock or
leakage.
3 Connect the interconnection cable and power supply as follows:
c
b
a
d
V3
1~ 50 Hz
230 V
W1
3N~ 50 Hz
400 V
L1 L3L2
L1 L3L2
a Interconnection cable
b Power supply cable
c Earth leakage circuit breaker
d Fuse
d
b
a
V3 W1
e
f
d
e
f
c c
a Switch box
b Stop valve attachment plate
c Earth
d Cable tie
e Interconnection cable
f Power supply cable
4 Fix the cables (power supply, interconnection cable and power
supply of the bottom plate heater (if applicable)) with a cable tie
to the stop valve attachment plate.
5 Route the wiring through the frame and connect it to it.