ROTEX HPSU low temperature Bi‑bloc
4P384980-1B – 2016.03
Routing through
the frame
Choose one of the 3 possibilities:
a
b
a
b
a
b
2
3
1
a Power supply, earth wiring, and bottom
plate heater wire (if applicable)
b Interconnection cable
Connecting to the
frame
When cables are routed from the unit, a
protection sleeve for the conduits (PG
insertions) can be inserted at the knockout
hole.
When you do not use a wire conduit,
protect the wires with vinyl tubes to
prevent the edge of the knockout hole from
cutting the wires.
a b c d e
A B
A Inside of the outdoor unit
B Outside of the outdoor unit
a Wire
b Bush
c Nut
d Frame
e Hose
6 Reattach the service cover. See "7.10.2 To close the outdoor
unit"on page46.
7 Connect an earth leakage circuit breaker and fuse to the power
supply line.
7.9.7 To reposition the air thermistor on the
outdoor unit
Required accessories:
Thermistor fixture.
Use the one from the accessory bag.
Thermistor fixing plate.
Reuse the one attached to the unit. If necessary,
you can use the spare one from the accessory
bag.
1
3
2
4
5
7
6
7
8
9
10
11
7.9.8 To connect the electrical wiring on the
indoor unit
1 To open the indoor unit, see "7.2.3To open the indoor unit"on
page29.
2 Wiring should enter the unit from the bottom.
3 Routing of the wiring inside the unit should be as follows: