Daikin EHVH08SU18DA6V7 [168/240] Configuration

Daikin EHVH08SU23DA6V7 [168/240] Configuration
8 | Configuration
Installer reference guide
168
ERGA04~08DAV3(A) + EHVH04+08SU18+23DA6V7
Daikin Altherma 3 R F
4P618956-1 – 2020.03
# Code Description
[9.6.3] [5-04] Offset BSH setpoint: Setpoint correction
for domestic hot water temperature: setpoint
correction for the desired domestic hot water
temperature, to be applied at low outdoor
temperature when space heating priority is
enabled. The corrected (higher) setpoint will
make sure that the total heat capacity of the
water in the tank remains approximately
unchanged, by compensating for the colder
bottom water layer of the tank (because the
heat exchanger coil is not operational) with a
warmer top layer.
Range: 0°C~20°C
Timers
For simultaneous space and domestic hot water operation request.
# Code Description
[9.6.4] [8-02] Anti-recycle timer: Minimum time
between two cycles for domestic hot water. The
actual anti-recycling time also depends on setting
[8-04].
Range: 0~10 hours
Remark: The minimum time is 0.5 hours even
when the selected value is 0.
[9.6.5] N/A Minimum running timer:
Do NOT change.
[9.6.6] [8-01] Maximum running timer for domestic hot
water operation. Domestic hot water heating
stops even when the target domestic hot water
temperature is NOT reached. The actual
maximum running time also depends on setting
[8-04].
When Control=Room thermostat: This
preset value is only taken into account if there
is a request for space heating or cooling. If
there is NO request for space heating/cooling,
the tank is heated until the setpoint has been
reached.
When ControlRoom thermostat: This
preset value is always taken into account.
Range: 5~95 minutes
[9.6.7] [8-04] Additional timer: Additional running time
for the maximum running time depending on the
outdoor temperature [4-02] or [F-01].
Range: 0~95 minutes
[8-02]: Anti-recycle timer