Daikin EHVH08SU18DA6V7 [21/240] Identification label indoor unit

Daikin EHVH08SU23DA6V7 [21/240] Identification label indoor unit
4 | About the units and options
Installer reference guide
21
ERGA04~08DAV3(A) + EHVH04+08SU18+23DA6V7
Daikin Altherma 3 R F
4P618956-1 – 2020.03
4.2.2 Identification label: Indoor unit
Location
Model identification
Example: EHVH08SU23DA6V
Code Description
E European model
HV Floor-standing indoor unit with integrated tank
H Heating only
08 Capacity class
S Integrated tank material: Stainless steel
U UK model
23 Integrated tank volume
DA Model series
6V Backup heater model
4.3 Combining units and options
INFORMATION
Certain options might not be available in your country.
4.3.1 Possible options for the outdoor unit
Drain pan kit (EKDP008D)
The drain pan kit is required to gather the drain from the outdoor unit. The drain
pan kit consists of:
Drain pan
Installation brackets
For installation instructions, see the installation manual of the drain pan.
Drain pan heater (EKDPH008CA)
The drain pan heater is required to avoid freezing-up of the drain pan.
It is recommended to install this option in colder regions with possible low ambient
temperatures or heavy snowfall.
For installation instructions, see the installation manual of the drain pan heater.
U-beams (EKFT008D)
The U-beams are installation brackets on which the outdoor unit can be installed.
It is recommended to install this option in colder regions with possible low ambient
temperatures or heavy snowfall.