Daikin EHVH08SU18DA6V7 [51/240] Preparation

Daikin EHVH08SU23DA6V7 [51/240] Preparation
6 | Preparation
Installer reference guide
51
ERGA04~08DAV3(A) + EHVH04+08SU18+23DA6V7
Daikin Altherma 3 R F
4P618956-1 – 2020.03
It is NOT recommended to install the unit in the following places because it may
shorten the life of the unit:
Where the voltage fluctuates a lot
In vehicles or vessels
Where acidic or alkaline vapour is present
Seaside installation. Make sure the outdoor unit is NOT directly exposed to sea
winds. This is to prevent corrosion caused by high levels of salt in the air, which
might shorten the life of the unit.
Install the outdoor unit away from direct sea winds.
Example: Behind the building.
b
c
a
If the outdoor unit is exposed to direct sea winds, install a windbreaker.
Height of windbreaker≥1.5×height of outdoor unit
Mind the service space requirements when installing the windbreaker.
a
b
c
d
c
d
a Sea wind
b Building
c Outdoor unit
d Windbreaker
The outdoor unit is designed for outdoor installation only, and for the following
ambient temperatures:
Cooling mode 10~43°C
Heating mode –25~25°C
6.2.2 Additional installation site requirements of the outdoor unit in cold climates
In areas with low ambient temperatures and high humidity, or in areas with heavy
snowfall, remove the suction grille to ensure proper operation.
Non-exhaustive list of areas: Austria, Czech Republic, Denmark, Estonia, Finland,
Germany, Hungary, Latvia, Lithuania, Norway, Poland, Romania, Serbia, Slovakia,
Sweden, …
1 Remove the screws holding the suction grille.
2 Remove the suction grille, and dispose of it.
3 Reattach the screws to the unit.