Daikin EKHWMX500CA — управление временем для отопительных систем: инструкции и программы [15/64]
Превью страниц
Страница 15 /
64
![Daikin EKHWMX500CA [15/64] X operation](/views2/1788392/page15/bgf.png)
3 x Operation
Daikin Control unit
RoCon mb
008.1446899_00 – 07/2019 – EN
Operating instructions
15
Permanent time programs
Time programs control the heating circuit temperatures or the op-
erating times of the circulation pump according to the specified
switching cycles for the connected heating circuits and the
storage charging circuit. The switching cycles are saved in time
blocks for which different target temperatures can be set.
In the switching cycles, the heating system is controlled differ-
ently according to day and reducing mode.
The target temperatures for these time programs are set in the
rotary switch positions "Set Temp Day"
, "Set Temp Night"
and "DHW Set Temp" .
The following switching time programs are available:
– 2 time programs for the heating circuit, each with 3 possi-
ble switching cycles
– [HC Program 1]
– [HC Program 2]
The times can be entered separately for each individual
weekday or in blocks of "Monday to Friday", "Saturday
to Sunday" and "Monday to Sunday".
Program Time period Switching cycle
HC Program 1
Individual weekday
(Monday, Tuesday …)
1.
2.
3.
06:00 -> 22:00
--:-- -> --:--
--:-- -> --:--
Working week
(Monday to Friday)
1.
2.
3.
06:00 -> 22:00
--:-- -> --:--
--:-- -> --:--
Weekend
(Saturday to Sunday)
1.
2.
3.
07:00 -> 23:00
--:-- -> --:--
--:-- -> --:--
Whole week
(Monday to Sunday)
1.
2.
3.
06:00 -> 22:00
--:-- -> --:--
--:-- -> --:--
HC Program 2
See
HC Program 1
1.
2.
3.
See
HC Program 1
Tab. 3-8 Menu structure of heating circuit/time program
Time settings for a switching cycle in a weekday or
block program will also be accepted for other time pe-
riods as long as they are for the same weekdays. Ex-
amples referring to tab. 3-8:
a) The starting time in the 1st switching cycle is changed from
06:00 am to 05:00 am for the individual weekday "Monday".
The 1st switching cycle is also automatically changed
from 06:00 am to 05:00 am for the "working week" and
"whole week" time periods.
b) The starting time in the 1st switching cycle is changed from
07:00 am to 08:00 am for the "weekend" time period.
The 1st switching cycle is also automatically changed
from 07:00 am to 08:00 am for the individual weekdays
"Saturday" and "Sunday".
c) The end time in the 1st switching cycle is changed from
10:00 pm to 9:30 pm for the "whole week" time period.
The 1st switching cycle is also automatically changed
from 10:00 pm to 9:30 pm in all weekday or block pro-
grams.
– 2 time programs for the hot water circuit, each with 3 pos-
sible switching cycles
– [DHW Program 1]
– [DHW Program 2]
The setting and the entry structure of the time programs
are identical with those for the heating circuit time
program (see also tab. 3-8).
– 1 time program for an optionally connected circulation
pump, each with 3 possible switching cycles
– [Circulation Time]
The setting and the entry structure of the time program
are identical with those for the heating circuit time pro-
gram (see also tab. 3-8).
For further information on settings for an optional circulation
pump, see chap. 3.6.15.
Saved switching time programs can be changed at any time. For
a better overview, it is recommended to write down and safely
store the programmed switching cycles (see chap. 9.1.1).
The permanent time programs are preset according to tab. 3-9.
Содержание
- Operating instructions p.1
- Electronic controller for heat pumps p.1
- Ekhwmx300c ekhwmxb300c ekhwmx500c ekhwmxb500c p.1
- Control unit rocon mb ehs157034 ehs157068 p.1
- Refer to the manual 4 p.2
- Errors malfunctions and messages 55 p.2
- Emergency operation 56 p.2
- Recognising errors correcting malfunctions 55 p.2
- Ehs157068 mixer module 51 p.2
- Warning signs and explanation of symbols 4 p.2
- Putting optional rocon system components into operation 33 p.2
- Commissioning daikin altherma m ec p.2
- Use as intended 5 p.2
- Product description 6 p.2
- Basic functions and operating modes 10 p.2
- Special system settings 21 p.2
- Parameter settings 40 p.2
- Avoiding danger 5 p.2
- Special functions 20 p.2
- Parameter overview 36 p.2
- After first commissioning after successful basic configuration 37 p.2
- Safety 4 p.2
- Parameter levels for the ehs157068 mixer module 38 p.2
- Rotary switch setting time program 49 p.2
- Operation 7 p.2
- Rotary switch setting set temp night 48 p.2
- Operating support during 1st commissioning and during system extensions 32 p.2
- Rotary switch setting set temp day 48 p.2
- Operating concept 9 p.2
- Rotary switch setting remote param 49 p.2
- List of contents p.2
- Rotary switch setting operating mode 48 p.2
- Initial start up 31 p.2
- Rotary switch setting info 49 6 1 exit key special function 50 6 2 basic configuration parameter level 51 6 3 parameter levels of the p.2
- General 7 p.2
- Rotary switch setting dhw set temp 48 p.2
- Fundamental aspects of the ids and authorisations in the rocon system 31 p.2
- Rotary switch setting dhw install 47 p.2
- For first commissioning or resetting to factory settings 36 p.2
- Rotary switch setting configuration 40 p.2
- Explanation of the parameter tables 40 p.2
- List of contents p.3
- Glossary 7 p.3
- Notes 8 p.3
- List of keywords 3 p.3
- X safety p.4
- X safety p.5
- X product description p.6
- Product description p.6
- X operation p.7
- The displays and the keys of the control unit must be protected against the effects of moisture to clean the control unit use a dry cotton cloth using aggressive cleaning agents and other fluids can cause damage to devices or lead to an electric shock p.7
- Operation p.7
- Maximum energy exploitation p.7
- If electrical components come into contact with water this can cause an electric shock as well as cause potentially fatal burns or injuries p.7
- General p.7
- Display and operating elements p.7
- Display p.7
- Danger p.7
- Caution p.8
- X operation p.8
- Rotary switch p.8
- Never operate the operating elements of the control unit with a hard pointed object this can cause damage and can cause the control to malfunction p.8
- Explanation of symbols p.8
- Controls p.8
- X operation p.9
- Rotary button p.9
- Operating concept p.9
- Exit key p.9
- X operation p.10
- System information info p.10
- Keylock p.10
- Basic functions and operating modes p.10
- Automatic defrost function p.10
- X operation p.11
- Displaying the operating data overview p.11
- X operation p.12
- Setting the operating mode p.12
- Operating mode standby stand by p.12
- Displaying the water pressure p.12
- Caution p.12
- Add glycol to the heating water circuit see installation and maintenance instructions alternatively drain the heating system on the water side if there is a danger of frost if the heating system is not drained the power supply must be ensured and the external main switch must remain switched on if there is a danger of frost p.12
- A heating system that is not protected against frost can freeze in the event of frost and thus be damaged p.12
- X operation p.13
- Operating mode summer p.13
- Operating mode reducing p.13
- Operating mode automatic 2 time program p.13
- Operating mode automatic 1 time program p.13
- Heating cooling p.13
- Temperature setting of daytime room temperature p.14
- Switching time program p.14
- Setting p.14
- X operation p.14
- Unscheduled hot water preparation p.14
- Temperature setting of setback mode p.14
- Temperature setting of hot water generation p.14
- X operation p.15
- Permanent time programs p.15
- X operation p.16
- Temporary time programs p.16
- X operation p.17
- Terminal function p.17
- System settings p.17
- Setting the lcd display language date time p.17
- During active whisper mode the output in room heating and room cooling mode decreases such that it may no longer be possible to achieve pre set target temperature values p.18
- Caution p.18
- Activating deactivating whisper mode p.18
- Activating deactivating terminal operation p.18
- X operation p.18
- With outside temperatures below freezing there is a risk of material damage caused by frost p.18
- Whisper mode p.18
- Operation with glycol p.18
- X operation p.19
- Warning p.19
- This storage tank charging is carried out even when standby operating mode is set p.19
- There is a danger of scalding at target hot water temperatures over 60 c this is possible as the utility company evu is entitled to control current draw optimised according to supply and demand in the definitions for smart grid p.19
- Smart grid sg p.19
- Install scald protection in the hot water distri bution line e g vta32 screw set 1 p.19
- Ehs emergency operation p.19
- Due to such forced charging the target hot water temperature in the hot water storage tank can exceed 60 c p.19
- Activating deactivating emergency automatic operation p.19
- Special functions p.20
- Manual operation p.20
- 3 way switching valves reference travel p.20
- X operation p.20
- X operation p.21
- Special system settings p.21
- Prior to initial commissioning of the floor heating system set the maximum temper ature limit in the rocon mb controller parameter t vbh1 max and the maximum permissible system temperature parameter max t flow connect an overheating protection switch in the building at the ext plug connection to external operating mode switch over so that the daikin altherma m ec p.21
- O is switched to standby or summer operating mode see chap 3 with parameter room thermostat on or parameter interlink fct on the overheating protection switch must be connected so that the room thermostat s switching contact is interrupted if the floor heating is also used for room cooling the connection notes in the above point also apply to the connection of a moisture protection switch in the building p.21
- In the event of malfunction or during manual operation the floor heating the screed or the floor structure could be damaged due to over heating p.21
- Heat slope p.21
- Expert p.21
- Caution risk of overheating of floor heating p.21
- Access rights technician code p.21
- X operation p.22
- Prior to initial commissioning and activation of cooling mode set the minimum temper ature limit to the minimum permissible system temperature in the rocon mb controller parameter min t flow cooling p.22
- Manually adjusting the heat slope p.22
- In the event of malfunction or incorrect parame ter settings the floor heating the screed or the floor structure could be damaged due to con densation p.22
- Cooling slope p.22
- Caution risk of condensation p.22
- X operation p.23
- With connected mixer module p.23
- Weather dependent t hs control p.23
- Frost protection function p.23
- X operation p.24
- Unsuitable feed temperatures can cause dam age to the floor heating system or dew formation on cooling surfaces p.24
- Limit target feed temperatures to suitable temperature ranges design heat distribution areas with different design temperatures as hydraulically separate heating circuits if necessary design heating circuits with lim ited target feed temperatures as mixer cir cuits and regulate with a mixer module p.24
- Interlink function p.24
- Caution p.24
- Additional alternative heat generator p.24
- X operation p.25
- Special function switching contacts p.25
- Heating support p.25
- Air purge p.25
- Install scald protection in the hot water distri bution line e g vta32 screw set 1 p.26
- Anti legionella system p.26
- X operation p.26
- Warning p.26
- There is a danger of scalding at target hot water temperatures over 60 c this is possible when using solar energy if the legionella protection or smart grid functions are activated or the target hot water temperature is set higher than 60 c p.26
- Resetting to factory settings reset p.26
- Option 3 p.26
- Option 2 p.26
- Option 1 p.26
- X operation p.27
- Screed program p.27
- Screed curing heating p.27
- Function heating p.27
- X operation p.28
- Setting and starting the screed program p.28
- Settings for optional circulation pump p.29
- Relay test p.29
- Defining the switching time program for the circulation pump p.29
- X operation p.29
- X operation p.30
- Remote control via internet p.30
- X initial start up p.31
- Initial start up p.31
- Fundamental aspects of the ids and authorisations in the rocon system p.31
- X initial start up p.32
- Operating support during 1st commissioning and during system extensions p.32
- For the ehs157034 room station p.32
- For all rocon b1 and ehs157034 control units p.32
- X initial start up p.33
- Putting optional rocon system components into operation p.33
- Mixer module ehs157068 p.33
- Commissioning daikin altherma m ec p.33
- Assigning the terminal id on the rocon b1 control panel of the daikin altherma m ec p.33
- A configuration for the living room setting p.34
- X initial start up p.34
- Sequence for initial commissioning see also chap 4 p.34
- Ehs157034 room station p.34
- B configuration for mixing valve setting p.34
- X initial start up p.35
- Master rocon function p.35
- Caretaker function p.35
- Allocating the ehs157068 mixing module to a heat generator p.35
- X parameter overview p.36
- Parameter overview p.36
- For first commissioning or resetting to factory settings p.36
- During initial commissioning after resetting to factory settings p.36
- X parameter overview p.37
- Rotary switch setting configuration p.37
- After first commissioning after successful basic configuration p.37
- Exit key special function p.38
- X parameter overview p.38
- See chap 5 p.38
- Rotary switch setting time program p.38
- Rotary switch setting set temp night p.38
- Rotary switch setting set temp day p.38
- Rotary switch setting remote param p.38
- Rotary switch setting operating mode p.38
- Rotary switch setting info p.38
- Rotary switch setting dhw set temp p.38
- Rotary switch setting dhw install p.38
- Parameter levels for the ehs157068 mixer module p.38
- No function p.38
- See chap 5 p.39
- Rotary switch setting time program p.39
- Rotary switch setting remote param p.39
- Rotary switch setting configuration p.39
- X parameter overview p.39
- Tab 5 12 parameters in the configuration rotary switch setting p.39
- X parameter settings p.40
- Setup level p.40
- Rotary switch setting configuration p.40
- Parameter settings p.40
- Explanation of the parameter tables p.40
- X parameter settings p.41
- X parameter settings p.42
- X parameter settings p.43
- Tab 6 1 parameters in the configuration rotary switch setting setup level p.43
- X parameter settings p.44
- System configuration level p.44
- Tab 6 2 parameters in the configuration rotary switch setting system configuration level p.45
- Hc configuration level p.45
- Depending on the version individual information pa rameters are displayed that are not described in tab 6 2 for this see tab 6 12 p.45
- X parameter settings p.45
- X parameter settings p.46
- X parameter settings p.47
- Rotary switch setting dhw install p.47
- Dhw configuration level p.47
- X parameter settings p.48
- Tab 6 9 parameters in the dhw set temp rotary switch setting p.48
- Tab 6 8 parameters in the set temp night rotary switch setting p.48
- Tab 6 7 parameters in the set temp day rotary switch setting p.48
- Tab 6 6 parameters in the operating mode rotary switch setting p.48
- Rotary switch setting set temp night p.48
- Rotary switch setting set temp day p.48
- Rotary switch setting operating mode p.48
- Rotary switch setting dhw set temp p.48
- Rotary switch setting remote param p.49
- Rotary switch setting info p.49
- X parameter settings p.49
- Tab 6 11 parameters in the remote param rotary switch setting p.49
- Tab 6 10 parameters in the time program rotary switch setting p.49
- Rotary switch setting time program p.49
- X parameter settings p.50
- To enter press the exit button for at least 5 s p.50
- Tab 6 13 parameters at the special level level p.50
- Tab 6 12 parameters in the info rotary switch setting p.50
- Exit key special function p.50
- Only the corresponding sections are referred to below signif icant differences are explained in more detail p.51
- X parameter settings p.51
- On setting a ehs157034 room station assigned to the mixer module via the heating circuit id to living room the parameter t room adj is available the target room temperature can be changed in the range 5 k to 5 k with the rotary button this function is not available if the ehs157034 is used as a remote control in terminal function p.51
- This parameter level only appears during initial commissioning if the answer selected for the use standard config prompt was no or p.51
- On setting a control panel to mix valve x terminal function the displayed values refer to the components pump mix valve connected to the ehs157068 of the mixer circuit assigned via the device id p.51
- The parameter levels parameter meanings setting ranges and connected functions are basically described in the same way as in the previous sections p.51
- No function p.51
- See chap 6 3 and 6 3 p.51
- Basic configuration parameter level p.51
- See chap 6 0 p.51
- See chap 6 p.51
- An unlimited scope of available parameters exists at the indi vidual levels p.51
- Rotary switch setting time program p.51
- After the system config parameter has been set to inactive or delete in the configuration rotary switch setting setup level p.51
- Rotary switch setting set temp night p.51
- Rotary switch setting set temp day p.51
- Rotary switch setting remote param p.51
- Rotary switch setting operating mode p.51
- Rotary switch setting info p.51
- Rotary switch setting dhw set temp p.51
- Rotary switch setting dhw install p.51
- Rotary switch setting configuration p.51
- Parameter levels of the ehs157068 mixer module p.51
- X parameter settings p.52
- Tab 6 15 parameters in the configuration rotary switch setting setup level p.52
- Rotary switch setting configuration setup level p.52
- X parameter settings p.53
- Rotary switch setting configuration mixer config level p.53
- X parameter settings p.54
- Tab 6 16 parameters in the configuration rotary switch setting mixer config level p.54
- X errors malfunctions and messages p.55
- Secure potential equalisation before touching electronic parts e g by touching an earthed metallic part p.55
- Recognising errors correcting malfunctions p.55
- Errors malfunctions and messages p.55
- Electrostatic charges can lead to voltage arcing that can destroy the electronic components p.55
- Caution p.55
- Malfunctions and fault codes p.56
- Emergency operation p.56
- Ehs emergency operation p.56
- X errors malfunctions and messages p.56
- X glossary p.57
- Glossary p.57
- X notes p.58
- User specific settings p.58
- Switching time program p.58
- X notes p.59
- Rocon device id comments p.59
- Parameters p.59
- O operating manual p.59
- Ids in the rocon can bus system p.59
- Enter the parameter changes you have made in the following table and in the daikin altherma m ec p.59
- Circulation time p.59
- X notes p.60
- Other items p.60
- X notes p.61
- X notes p.62
- X list of keywords p.63
- List of keywords p.63
Похожие устройства
-
Daikin EVLQ08CAV3Руководство по применению для установщика -
Daikin EVLQ08CAV3Справочное руководство для монтажника -
Daikin EVLQ08CAV3Общие правила техники безопасности -
Daikin EVLQ08CAV3Инструкция по монтажу -
Daikin EVLQ05CAV3Справочное руководство для монтажника -
Daikin EVLQ05CAV3Руководство по применению для установщика -
Daikin EVLQ05CAV3Общие правила техники безопасности -
Daikin EVLQ05CAV3Инструкция по монтажу -
Daikin EHYKOMB33AA3Справочное руководство для монтажника -
Daikin EHYKOMB33AA3Руководство по применению для установщика -
Daikin EHYKOMB33AA3Руководство по эксплуатации -
Daikin EHYKOMB33AA2Руководство по применению для установщика
Изучите управление временем для отопительных систем с помощью программирования температур и циклов. Оптимизируйте работу вашего отопления и горячего водоснабжения.