[2] Disinfection function
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by
periodically heating the domestic hot water to a specific temperature.
■ [2-00] Operation interval: day(s) of the week at which the
domestic hot water should be heated.
■ [2-01] Status: defines whether the disinfection function is
turned on (1) or off (0).
■ [2-02] Start time: time of the day at which the domestic hot
water should be heated.
■ [2-03] Set point: high water temperature to be reached.
■ [2-04] Interval: time period defining how long the set point
temperature should be maintained.
T
DHW
Domestic hot water temperature
T
U
User set point temperature (as set on the user interface)
T
H
High set point temperature [2-03]
t Time
[3] Auto restart
When power returns after a power supply failure, the auto restart
function reapplies the user interface settings at the time of the power
supply failure.
Note that with the function disabled the schedule timer will not be
activated when power returns to the unit after a power supply failure.
Press the pr button to enable the schedule timer again.
■ [3-00] Status: defines whether the auto restart function is
turned ON (0) or OFF (1).
[4] Space heating off temperature
Space heating off temperature
■ [4-02] Space heating off temperature: outdoor temperature
above which space heating is turned off to avoid overheating.
[6] Scheduled storage and reheat domestic water heating
Scheduled domestic hot water storage
The storage set point can be accessed directly using the
wi and
wj buttons.
■ [6-03] Scheduled storage: defines whether the scheduled
domestic water heating storage during night is enabled (1) or
not (0).
■ [6-04] Scheduled storage start time: time of the night at which
the domestic water should be heated.
CAUTION
The disinfection function field settings must be configured
by the installer according to the applicable legislation.
WARNING
Be aware that the domestic hot water temperature at the
hot water tap will be equal to the value selected in field
setting [2-03] after a disinfection operation.
When the high domestic hot water temperature can be a
potential risk for human injuries, a mixing valve (field
supply) shall be installed at the hot water outlet connection
of the domestic hot water tank. This mixing valve shall
secure that the hot water temperature at the hot water tap
never rises above a set maximum value. This maximum
allowable hot water temperature shall be selected
according to the applicable legislation.
CAUTION
Make sure that the disinfection function start time [2-02]
with defined duration [2-04] is not interrupted by possible
domestic hot water demand.
00.00 22.00 24.0001.00 23.00 t
T
DHW
T
H
T
U
[2-02]
[2-03]
[2-04]
NOTICE
It is therefore recommended to leave the auto restart
function enabled.
NOTICE
If the benefit kWh rate power supply is of the type that
power supply is interrupted, then always allow the auto
restart function.
If you feel unsure about this topic, contact your installer for
advice and information.
INFORMATION
The scheduled storage and reheat domestic water heating
will only be carried out when [4-03]=4 and the domestic
water heating mode is enabled by the w button.
Содержание
- Operation manual 1
- Unit for air to water heat pump system 1
- Definitions 2
- Efinitions 2
- Meaning of used terms 2
- Meaning of warnings and symbols 2
- Operation manual 2
- Afety precautions 3
- General safety precautions 3
- Introduction 3
- Ntroduction 3
- This manual 3
- This unit 3
- Features and functions 4
- Introduction 4
- Operating the digital controller 4
- Operating the unit 4
- Perating the unit 4
- Name and function of buttons and icons 5
- Setting the clock 6
- Setting the schedule timer 6
- Setting up the controller 6
- Description of the operation modes 7
- Domestic water heating operation 7
- Domestic water heating operation w 7
- Powerful domestic water heating operation 7
- Space cooling operation 7
- Space cooling operation c 7
- Space heating operation 7
- Space heating operation h 7
- Controller operations 8
- Manual operation 8
- Quiet mode operation 8
- Quiet mode operation s 8
- Schedule timer operation 9
- Getting started 10
- Programming and consulting the schedule timer 10
- Programming 11
- Consulting programmed actions 13
- Tips and tricks 13
- Field settings 14
- Ield settings 14
- Procedure 14
- Detailed description 15
- Field settings table 19
- Aintenance 21
- Disposal requirements 21
- Important information regarding the refrigerant used 21
- Isposal requirements 21
- Maintenance 21
- Maintenance activities 21
- Roubleshooting 21
- Standstill 21
- Troubleshooting 21
Похожие устройства
- Daikin EKCBH008BCV3 Инструкция по монтажу
- Daikin BEVN32AV1 Инструкция по монтажу
- Daikin BEVN50AV1 Инструкция по монтажу
- Daikin BEVN125AV1 Инструкция по монтажу
- Daikin BRC1E53A7 Инструкция по монтажу
- Daikin BRC1E53A7 Руководство по применению для установщика
- Daikin BRC1E53A7 Руководство по применению для пользователя
- Daikin BRC1E53B Инструкция по монтажу
- Daikin BRC1E53B Руководство по применению для установщика
- Garmin echo 200 Инструкция по эксплуатации
- Garmin echo 200 Инструкция по установке
- Samsung VP-DC575Wi Инструкция по эксплуатации
- Samsung VP-DC575WB Инструкция по эксплуатации
- Samsung VP-DC565WB(i) Инструкция по эксплуатации
- Samsung VP-DC565W(i) Инструкция по эксплуатации
- Samsung VP-DC563(i) Инструкция по эксплуатации
- Samsung VP-DC175WB Инструкция по эксплуатации
- Samsung VP-DC175W(i) Инструкция по эксплуатации
- Samsung VP-DC173(i) Инструкция по эксплуатации
- Samsung VP-DC172W Инструкция по эксплуатации