Operation manual
19
EKCBX/H008BCV3
Unit for air to water heat pump system
4P348534-1 – 2013.04
8 Installation related setting
00 Installation related setting
01 Installation related setting
02 Installation related setting
03 Installation related setting
04 Installation related setting
9 Heating and cooling set point ranges
00 Heating set point upper limit
55 37~55 1 °C
01 Heating set point lower limit
25 15~37 1 °C
02 Cooling set point upper limit
22 18~22 1 °C
03 Cooling set point lower limit
5 5~18 1 °C
04 Installation related setting
Automatic set back function
05 Set back operation
0 (OFF) 0/1 1
06 Set back operation start time
23:00 0:00~23:00 1:00 hour
07 Set back operation stop time
5:00 0:00~23:00 1:00 hour
08 Leaving water set back value
2 0~10 1 °C
C Solar kit
00 Solar priority mode setting
0 0/1 1
01 Installation related setting
02 Installation related setting
03 Installation related setting
04 Installation related setting
05 Not applicable. Do not change the default setting.
——
d Local shift value weather dependent
00 Installation related setting
01 Installation related setting
02 Installation related setting
03 Local shift value weather dependent
0 (OFF) 0/1/2/3/4 1
04 Not applicable. Do not change the default value.
——
05 Installation related setting
06 Not applicable. Do not change the default value.
——
E Unit information readout
00 Software version
Read only
01 EEPROM version
Read only
02 Unit model identification. depending
on model
——
03 Liquid refrigerant temperature
Read only 1 °C
04 Inlet water temperature
Read only 1 °C
F Installation related setting
00 Installation related setting
01 Installation related setting
02 Installation related setting
03 Installation related setting
04 Installation related setting
Installation related setting
05 Installation related setting
06 Installation related setting
07 Installation related setting
08 Installation related setting
09 Installation related setting
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value