8 Troubleshooting
Installation and operation manual
22
RXYTQ8~16T7YF
VRV IV system air conditioner
4P388987-1C – 2016.02
Additional refrigerant charge
The amount of refrigerant to be added to the unit shall be
written on the included "Added refrigerant" plate and
attached to the rear side of the front cover.
Installation date and field setting
Be sure to keep record of the installation date on the
sticker on the rear of the upper front panel according to
EN60335‑2‑40 and keep record of the contents of the field
setting(s).
7.3 About test run
The procedure below describes the test operation of the complete
system. This operation checks and judges following items:
▪ Check of wrong wiring (communication check with indoor units).
▪ Check of the stop valves opening.
▪ Judgement of piping length.
▪ Make sure to carry out the system test operation after the first
installation. Otherwise, the malfunction code will be displayed
on the user interface and normal operation or individual indoor unit
test run cannot be carried out.
▪ Abnormalities on indoor units cannot be checked for each unit
separately. After the test operation is finished, check the indoor
units one by one by performing a normal operation using the user
interface. Refer to the indoor unit installation manual for more
details concerning the individual test run.
INFORMATION
▪ It may take 10 minutes to achieve a uniform refrigerant
state before the compressor starts.
▪ During the test operation, the refrigerant running sound
or the magnetic sound of a solenoid valve may become
loud and the display indication may change. These are
not malfunctions.
7.4 To perform a test run
1 Close all front panels in order to not let it be the cause of
misjudgement (except the electrical component box inspection
opening service cover).
2 Make sure all field settings you want are set; see "6.1 Making
field settings"on page18.
3 Turn ON the power to the outdoor unit and the connected
indoor units.
NOTICE
Be sure to turn on the power 6 hours before operation in
order to have power running to the crankcase heater and
to protect the compressor.
4 Make sure the default (idle) situation is existing; see "6.1.4To
access mode 1 or 2"on page19. Push BS2 for 5 seconds or
more. The unit will start test operation.
Result: The test operation is automatically carried out, the
outdoor unit display will indicate " " and the indication "Test
operation" and "Under centralised control" will display on the
user interface of indoor units.
Steps during the automatic system test run procedure:
Step Description
Control before start up (pressure equalisation)
Cooling start up control
Step Description
Cooling stable condition
Communication check
Stop valve check
Pipe length check
Refrigerant amount check
Pump down operation
Unit stop
Note: During the test operation, it is not possible to stop the unit
operation from a user interface. To abort the operation, press BS3.
The unit will stop after ±30 seconds.
5 Check the test operation results on the outdoor unit 7‑segment
display.
Completion Description
Normal completion No indication on the 7‑segment display (idle).
Abnormal
completion
Indication of malfunction code on the
7‑segment display.
Refer to "7.5Correcting after abnormal
completion of the test run"on page22 to take
actions for correcting the abnormality. When
the test operation is fully completed, normal
operation will be possible after 5 minutes.
7.5 Correcting after abnormal
completion of the test run
The test operation is only completed if there is no malfunction code
displayed on the user interface or outdoor unit 7‑segment display. In
case of a displayed malfunction code, perform correcting actions as
explained in the malfunction code table. Carry out the test operation
again and confirm that the abnormality is properly corrected.
INFORMATION
Refer to the installation manual of the indoor unit for other
detailed malfunction codes related to indoor units.
8 Troubleshooting
8.1 Solving problems based on error
codes
In case of a displayed malfunction code, perform correcting actions
as explained in the malfunction code table.
After correcting the abnormality, press BS3 to reset the malfunction
code and retry operation.
The malfunction code which is displayed on the outdoor unit will
indicate a main malfunction code and a sub code. The sub code
indicates more detailed information about the malfunction code. The
malfunction code will be displayed intermittent.
Example:
Code Example
Main code
Sub code
With an interval of 1 second, the display will switch between main
code and sub code.
Содержание
- Installation and operation 1
- Manual 1
- Vrv iv system air conditioner 1
- About the box 3 2
- About the documentation 3 2
- About the system 28 2
- About the units and options 4 2
- Commissioning 21 2
- Configuration 18 2
- For the installer 3 2
- For the user 28 2
- Installation 7 2
- Installation and operation manual 2
- Maintenance and service 30 2
- Operation 28 2
- Preparation 4 2
- Table of contents 2
- Technical data 25 2
- Troubleshooting 22 2
- Troubleshooting 31 2
- User interface 28 2
- About the box 3
- About the documentation 3
- About this document 3
- Accessory pipes diameters 3
- After filling in this table please put it on the switch box cover 3
- Be sure to fill out the blanks which are needed for after sale services 3
- Calculation of additional refrigerant charging amount 3
- Disposal 33 3
- For details concerning piping selection and calculation or how to operate the leak detection function please refer to the installation manual 3
- For the installer 3
- Id øa 3
- Id øb 3
- Od øb 3
- Outdoor unit 3
- Record for settings contents see installation manual 3
- Record of additional refrigerant charge amount and result of leak check operation 3
- Record of indoor unit model and installation site 3
- Relocation 33 3
- To remove the accessories from the outdoor unit 3
- To remove the transportation stay 3
- About the outdoor unit 4
- About the units and options 4
- Additional installation site requirements of the outdoor unit in cold climates 4
- Installation site requirements of the outdoor unit 4
- Preparation 4
- Preparing installation site 4
- Preparing refrigerant piping 4
- Refrigerant piping requirements 4
- System layout 4
- A b b b 5
- A b c piping between outdoor unit and first refrigerant branch kit 5
- A e b c 5
- D piping between refrigerant branch kits 5
- E piping between refrigerant branch kit and indoor unit 5
- Preparation 5
- To select the piping size 5
- Multiple outdoor units possible layouts 6
- Preparation 6
- To select refrigerant branch kits 6
- Installation 7
- Opening the units 7
- Preparing electrical wiring 7
- Safety device requirements 7
- To open the electrical component box of the outdoor unit 7
- To open the outdoor unit 7
- Connecting the refrigerant piping 8
- Installation 8
- Mounting the outdoor unit 8
- To provide the installation structure 8
- To route the refrigerant piping 8
- Installation 9
- Multiple outdoor units knockout holes 9
- To connect the multi connection piping kit 9
- To connect the refrigerant piping to the outdoor unit 9
- To handle the stop valve 9
- To open the stop valve 9
- To protect against contamination 9
- Using the stop valve and service port 9
- Installation 10
- Tightening torques 10
- To close the stop valve 10
- To handle the service port 10
- To handle the stop valve cover 10
- To remove the pinched pipes 10
- About checking the refrigerant piping 11
- Checking refrigerant piping general guidelines 11
- Checking refrigerant piping setup 11
- Checking the refrigerant piping 11
- Installation 11
- Charging refrigerant 12
- Installation 12
- Precautions when charging refrigerant 12
- To check for leaks pressure leak test 12
- To check for leaks vacuum leak test 12
- To insulate the refrigerant piping 12
- To perform a leak test 12
- To perform vacuum drying 12
- About charging refrigerant 13
- Installation 13
- To charge refrigerant flow chart 13
- To determine the additional refrigerant amount 13
- Charging refrigerant 14
- Installation 14
- Pre charging refrigerant 14
- Installation 15
- Step 6 to manually charge refrigerant 15
- To charge refrigerant 15
- Checks after charging refrigerant 16
- Connecting the electrical wiring 16
- Error codes when charging refrigerant 16
- Field wiring overview 16
- Guidelines when knocking out knockout holes 16
- Installation 16
- To route and fix the transmission wiring 16
- A b c d e 17
- D d e f 17
- Hp 10 16 hp 17
- Installation 17
- To connect the power supply 17
- To connect the transmission wiring 17
- To finish the transmission wiring 17
- To route and fix the power supply 17
- A b c d 18
- About making field settings 18
- Configuration 18
- Field setting components 18
- J k h i 18
- Making field settings 18
- Configuration 19
- To access mode 1 or 2 19
- To access the field setting components 19
- To use mode 1 19
- To use mode 2 19
- Configuration 20
- Mode 1 monitoring settings 20
- Mode 2 field settings 20
- Checklist before commissioning 21
- Commissioning 21
- Precautions when commissioning 21
- About test run 22
- Correcting after abnormal completion of the test run 22
- Solving problems based on error codes 22
- To perform a test run 22
- Troubleshooting 22
- Error codes overview 23
- Troubleshooting 23
- Troubleshooting 24
- Service space outdoor unit 25
- Technical data 25
- Further specifications can be found in the technical engineering data 26
- In case of an installation site where only the sides a b have 26
- In case of an installation site where sides a b c d have 26
- Information 26
- Mm to avoid accumulation of ice in between the outdoor units 26
- Obstacles the wall heights have no influence on any indicated service space dimensions 26
- Obstacles the wall heights of sides a c have no impact on service space dimensions refer to the figure above for impact of wall heights of sides b d on service space dimensions 26
- Piping diagram outdoor unit 26
- Piping diagram rxytq10 12 26
- Piping diagram rxytq8 26
- Technical data 26
- The installation space required on these drawings are for full load 26
- The service space dimensions in above figure are based on cooling operation at 46 c ambient temperature standard conditions 26
- Piping diagram rxytq14 16 27
- Technical data 27
- About cooling heating fan only and automatic operation 28
- About operating the system 28
- About the heating operation 28
- About the system 28
- For the user 28
- Operating the system 28
- Operation 28
- Operation range 28
- To operate the system without cool heat changeover remote control switch 28
- User interface 28
- About the air flow flap 29
- About the dry program 29
- Adjusting the air flow direction 29
- Operation 29
- To operate the system with cool heat changeover remote control switch 29
- To use the dry program with cool heat changeover remote control switch 29
- To use the dry program without cool heat changeover remote control switch 29
- Using the dry program 29
- About setting the master user interface 30
- About the refrigerant 30
- After sales service and warranty 30
- Maintenance and service 30
- Setting the master user interface 30
- Warranty period 30
- Error codes overview 31
- Recommended maintenance and inspection 31
- Troubleshooting 31
- Symptom cool heat cannot be changed over 32
- Symptom fan operation is possible but cooling and heating do not work 32
- Symptom the fan strength does not correspond to the setting 32
- Symptom the system does not operate 32
- Symptoms that are not air conditioner troubles 32
- Troubleshooting 32
- 0 symptom noise of air conditioners 33
- 1 symptom noise of air conditioners 33
- 2 symptom dust comes out of the unit 33
- 3 symptom the units can give off odours 33
- 4 symptom the outdoor unit fan does not 33
- 5 symptom the display shows 88 33
- 6 symptom the compressor in the outdoor 33
- 7 symptom the inside of an outdoor unit is 33
- 8 symptom hot air can be felt when the 33
- Disposal 33
- Indoor unit is stopped 33
- Indoor unit outdoor unit 33
- Outdoor unit 33
- Relocation 33
- Symptom noise of air conditioners indoor unit 33
- Symptom the fan direction does not correspond to the setting 33
- Symptom the user interface display reads u4 or u5 and stops but then restarts after a few minutes 33
- Symptom white mist comes out of a unit indoor unit 33
- Symptom white mist comes out of a unit indoor unit outdoor unit 33
- Unit does not stop after a short heating operation 33
- Warm even when the unit has stopped 33
- Copyright 2015 daikin 36
- P388987 1c 36
Похожие устройства
- Daikin RXYTQ48TYF Руководство по применению для установщика
- Daikin RXYTQ8U7YF Общие правила техники безопасности
- Daikin RXYTQ10U7YF Общие правила техники безопасности
- Daikin RXYTQ8U7YF Инструкция по эксплуатации
- Daikin RXYTQ8U7YF Руководство по эксплуатации
- Daikin RXYTQ10U7YF Инструкция по эксплуатации
- Daikin RXYTQ8U7YF Руководство по применению для установщика
- Daikin RXYTQ10U7YF Руководство по эксплуатации
- Daikin RXYTQ10U7YF Руководство по применению для установщика
- Daikin RXYTQ12U7YF Общие правила техники безопасности
- Daikin RXYTQ12U7YF Инструкция по эксплуатации
- Daikin RXYTQ12U7YF Руководство по эксплуатации
- Daikin RXYTQ12U7YF Руководство по применению для установщика
- Daikin RXYTQ14U7YF Общие правила техники безопасности
- Daikin RXYTQ14U7YF Инструкция по эксплуатации
- Daikin RXYTQ14U7YF Руководство по эксплуатации
- Daikin RXYTQ14U7YF Руководство по применению для установщика
- Daikin RXYTQ16U7YF Общие правила техники безопасности
- Daikin RXYTQ16U7YF Инструкция по эксплуатации
- Daikin RXYTQ16U7YF Руководство по эксплуатации