Daikin ADEQ100A7VEB [6/12] Indoor unit installation
![Daikin ADEQ100A7VEB [6/12] Indoor unit installation](/views2/1792257/page6/bg6.png)
Installation manual
3
ADEQ71~125A7VEB
Split System air conditioners
4P335705-1 – 2012.11
2. The fan speed for this indoor unit is preset to provide standard
external static pressure.
If higher or lower external static pressure is required, reset the
external static pressure by changing the initial setting from the
remote controller.
Refer to "External static pressure setting using the remote
controller" on page 7.
3. Install the suspension bolts.
(Use M10 size bolt for the suspension bolt.) Use anchors for
existing ceilings, and a sunken insert, sunken anchors or other
field supplied parts for new ceilings to reinforce the ceiling in
order to bear the weight of the unit.
Installation example
(See figure 3)
INDOOR UNIT INSTALLATION
When installing optional accessories, read also the installation
manual of the optional accessories. Depending on the field
conditions, it may be easier to install optional accessories before the
indoor unit is installed.
1. Install the indoor unit temporarily.
• Attach the hanger bracket to the suspension bolt. Be sure to
fix it securely by using a nut and washer from the upper and
lower sides of the hanger bracket. (See figure 4)
2. Check if the unit is horizontally levelled.
• Do not install the unit tilted. The indoor unit is equipped with a
built-in drain pump and float switch.
(If the unit is tilted against condensate flow, the float switch
may malfunction and cause water to drip.)
• Check if the unit is levelled at all four corners with a water
level or a water-filled vinyl tube as shown in figure 8.
3. Tighten the upper nut.
REFRIGERANT PIPING WORK
For refrigerant piping of outdoor unit, refer to the installation manual
supplied with the outdoor unit.
Execute heat insulation work completely on both sides of the gas
piping and the liquid piping. Otherwise, this can sometimes result in
water leakage.
Before rigging tubes, check which type of refrigerant is used.
■ Use a pipe cutter and flare suitable for the used refrigerant.
■ To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.
■ Use copper alloy seamless pipes (ISO 1337).
■ The outdoor unit is charged with refrigerant.
■ To prevent water leakage, execute heat insulation work
completely on both sides of the gas and liquid piping. When
using a heat pump, the temperature of the gas piping can reach
up to approximately 120°C, use insulation which is sufficiently
heat resistant.
■ Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.
■ Do not mix anything other than the specified refrigerant, such as
air, etc..., inside the refrigerant circuit.
■ Use annealed material only for flare connections.
■ Refer to Table 1 for the dimensions of flare nut spaces and the
appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)
Table 1
■ When connecting the flare nut, coat the flare inner surface with
ether oil or ester oil and initially tighten 3 or 4 turns by hand
before tightening firmly.
■ If the refrigerant gas leaks during the work, ventilate the area. A
toxic gas is emitted by the refrigerant gas being exposed to a fire.
■ Make sure there is no refrigerant gas leak. A toxic gas may be
released by the refrigerant gas leaking indoor and being
exposed to flames from an area heater, cooking stove, etc.
NOTE
When installing an air inlet duct, select fixing screws
that shall stick out maximum 5 mm at the inside of the
flange to protect the air filter from damage during
maintenance of the filter.
1 Air inlet duct
2 Inside of the flange
3 Fixing screw
NOTE
For other installation than standard installation, contact
your Daikin dealer for details.
1 Anchor
2 Ceiling slab
3 Long nut or turn-buckle
4 Suspension bolt
5 Indoor unit
NOTE
All the above parts are field supplied.
1 Nut (field supply)
2 Washer for hanger bracket (supplied with the unit)
3 Tighten (double nut)
1 Water level
2 Vinyl tube
12
3
≤5 mm
All field piping must be provided by a licensed refrigeration
technician and must comply with the relevant local and
national codes.
1 Torque wrench
2 Spanner
3 Piping union
4 Flare nut
Pipe
gauge
Tightening torque
(N•m)
Flare dimension
A (mm)
Flare shape
Ø9.5 33~39 12.8~13.2
Ø15.9 63~75 19.3~19.7
12
4
3
R0.4~0.8
45°
±2
90°
±2
A
Содержание
- Installation manual 1
- Split system air conditioners 1
- Adeq71a7veb adeq100a7veb adeq125a7veb 3
- Daikin europe n v 3
- Director 3
- Electromagnetic compatibility 2004 108 ec 3
- En60335 2 4 3
- Jean pierre beuselinck 3
- Low voltage 2006 95 ec 3
- Machinery 2006 42 ec 3
- Ostend 1st of february 2013 3
- P335707 1 3
- P335707 1_adeq71 125a7veb fm page 1 monday november 26 2012 11 00 am 3
- Accessories 4
- Before installation 4
- Efore installation 4
- Installation manual 4
- Optional accessories 4
- Precautions 4
- Electing installation sit 5
- For the following items take special care during construction and check after installation is fi 5
- For the following items take special care during construction and check after installation is finished 5
- Installation with rear duct and duct service opening see figure 6b 5
- Installation with rear duct no duct service opening see figure 6c 5
- Notes to the installer 5
- Preparations before installation 5
- Reparations before installation 5
- Selecting installation site 5
- Standard rear suction see figure 6a 5
- Efrigerant piping work 6
- Indoor unit installation 6
- Ndoor unit installation 6
- Refrigerant piping work 6
- Cautions for brazing 7
- Drain piping work 7
- Rain piping work 7
- Electric wiring work 8
- General instructions 8
- Lectric wiring work 8
- Testing of drain piping 8
- When electric wiring work is not finished 8
- When electric wiring work is finished 8
- Electrical characteristics 9
- How to connect wiring 9
- Iring example and how to set the remote controller 9
- Precautions 9
- Specifications for field wire 9
- Specifications for field wire 9
- Wiring example and how to set the remote controller 9
- Complete system example 3 systems 10
- Control by 2 remote controllers controlling 1 indoor unit by 2 remote controllers 10
- External static pressure setting using the remote controller 10
- Field setting 10
- Iring example 10
- Precautions 10
- Setting air filter sign 10
- Setting air filter sign 10
- Setting for optional accessories 10
- Wiring example 10
- Est operation 11
- Iring diagram 11
- Test operation 11
- Wiring diagram 11
Похожие устройства
- Daikin ADEQ100A7VEB Инструкция по эксплуатации
- Daikin ADEQ125A7VEB Инструкция по монтажу
- Daikin ADEQ125A7VEB Инструкция по эксплуатации
- Daikin ADEQ71B2VEB Инструкция по эксплуатации
- Daikin ADEQ71B2VEB Инструкция по монтажу
- Daikin ADEQ100B2VEB Инструкция по эксплуатации
- Daikin ADEQ100B2VEB Инструкция по монтажу
- Daikin ADEQ125B2VEB Инструкция по эксплуатации
- Daikin ADEQ125B2VEB Инструкция по монтажу
- Daikin ADEQ35C2VEB Инструкция по монтажу
- Daikin ADEQ35C2VEB Инструкция по эксплуатации
- Daikin ADEQ50C2VEB Инструкция по монтажу
- Daikin ADEQ50C2VEB Инструкция по эксплуатации
- Daikin ADEQ60C2VEB Инструкция по монтажу
- Daikin ADEQ60C2VEB Инструкция по эксплуатации
- Daikin ADEQ71C2VEB Инструкция по монтажу
- Daikin ADEQ71C2VEB Инструкция по эксплуатации
- Daikin ADEQ100C2VEB Инструкция по монтажу
- Daikin ADEQ100C2VEB Инструкция по эксплуатации
- Daikin ADEQ125C2VEB Инструкция по монтажу