VACUUMING AND CHARGING
Vacuuming is necessary to eliminate all moisture and air from the system. The series II Outdoor Unit is provided with Á are
valve À ttings.
Vacuuming The Piping And The Indoor Unit
Except for the outdoor unit which is pre-charged with
refrigerant, the indoor unit and the refrigerant connection
pipes must be air-purged because the air containing moisture
that remains in the refrigerant cycle may cause malfunction
of the compressor.
• Remove the caps from the valve and the service port.
• Connect the center of the charging gauge to the vacuum
pump.
• Connect the charging gauge to the service port of the 3-way
valve.
• Start the vacuum pump. Evacuate for approximately 30
minutes. The evacuation time varies with different vacuum
pump capacity. ConÀ rm that the charging gauge needle has
moved towards -760mmHg.
Caution
• If the gauge needle does not move to -760mmHg, be sure to
check for gas leaks (using the refrigerant detector) at Á are
type connection of the indoor and outdoor unit and repair
the leak before proceeding to the next step.
• Close the valve of the changing gauge and stop the vacuum
pump.
• On the outdoor unit, open the suction valve (3 way) and
liquid valve (2 way) (in anti-clockwise direction) with 4mm
key for hexagon sacked screw.
Charge Operation
This operation must be done by using a gas cylinder and a
precise weighing machine. The additional charge is topped-up
into the outdoor unit using the suction valve via the service
port.
• Remove the service port cap.
• Connect the low pressure side of the charging gauge to the
suction service port center of the cylinder tank and close
the high pressure side of the gauge. Purge the air from the
service hose.
• Start the air conditioner unit.
• Open the gas cylinder and low pressure charging valve.
• When the required refrigerant quantity is pumped into
the unit, close the low pressure side and the gas cylinder
valve.
• Disconnect the service hose from service port. Put back the
service port cap.
Refrigerant Piping
Outdoor Unit 3 ways valve
Service Port
Allen key
Flare nut
LOW PRESSURE GAUGE HIGH PRESSURE GAUGE
GAUGE MANIFOLD
-760mmHg
HANDLE HI (ALWAYS CLOSED)
HANDLE LO
CHARGE HOSE
CHARGE HOSE
VACUUM PUMP ADAPTER FOR
COUNTER FLOW PREVENTION
CHECK VALVE
LIQUID VALVE
GAS VALVE (3-WAY)
CONFIGURATION OF AIR
P
U
R
G
E BY
C
HAR
G
I
NG
LOW PRESSURE GAUGE
HIGH PRESSURE GAUGE
GAUGE MANIFOLD
-760mmHg
HANDLE HI (ALWAYS CLOSED)
HANDLE LO
CHARGE HOSE
CHARGE HOSE
LIQUID VALVE
GAS VALVE (3-WAY)
CHECK VALVE
CONFIGURATION OF AIR
P
U
R
G
E BY
C
HAR
G
I
NG
1 IM-CCC-0311(0)-DAIKIN (SASO).i18 18 6/9/11 10:07:41 AM
Содержание
- Installation manual 1
- R22 split series 1
- English 3
- Outline and dimensions 3
- English 5
- Disposal requirements 6
- Installation and maintenance should be performed by quali ed persons who are familiar with local code and regulation and experienced with this type of appliance all eld wiring must be installed in accordance with the national wiring regulation ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work according to the wiring diagram the unit must be grounded to prevent possible hazard due to insulation failure all electrical wiring must not touch the refrigerant piping or any moving parts of the fan motors con rm that the unit has been switched off before installing or servicing the unit disconnect from the main power supply before servicing the air conditioner unit do not pull out the power cord when the power is on this may cause serious electrical shocks which may result in re hazards keep the indoor and outdoor units power cable and transmission wiring at least 1m from tvs and radios to prevent distorted pictures and static dependi 6
- Installation manual 6
- Notice 6
- Safety precautions 6
- This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit special adjustment may be necessary to suit local requirements before using your air conditioner please read this instruction manual carefully and keep it for future reference this appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons 6
- Warning caution 6
- English 7
- For model fd y m20jevlk fd y m25jevlk 7
- For model fd y m30jevlk fd y m40jevlk 7
- Important sequence as follow 7
- For model fr y m50jevlk fd y m60jevlk 8
- For model r y d20jevlk r y d25jevlk r y d30jevlk r y d40jevlk r y d50jetlk r y d60jetlk 8
- English 9
- Indoor unit 9
- Installation diagram 9
- Outdoor unit 9
- Installation of the indoor unit 10
- Ceiling concealed drain piping work 11
- English 11
- Caution 12
- Installation of the outdoor unit 12
- English 13
- Installation clearance 13
- Maximum pipe length 13
- Refrigerant piping 13
- Piping connection to the units 14
- Piping works and flaring technique 14
- Electrical connection 15
- English 15
- English 17
- English 19
- Charge operation 20
- Vacuuming and charging 20
- Vacuuming the piping and the indoor unit 20
- Additional charge 21
- Caution 21
- English 21
- Special precautions when charging unit with scroll compressors 22
- Caution 23
- English 23
- Indicator lights 23
- Operating range 24
- Overall checking 24
- Phase protector optional 24
- Caution 25
- English 25
- For any enquiries on spare part please contact your authorized dealer when any malfunction of the air conditioner unit is noted immediately switch off the power supply to the unit check the following fault conditions and causes for some simple troubleshooting tips 25
- If the fault persists please call your local dealer serviceman 25
- Service and maintenance 25
- Troubleshooting 25
- Specifications 26
- English 27
- Specifications 27
- Specifications 28
Похожие устройства
- Daikin FDYM60JEVLK Инструкция по эксплуатации
- Daikin FDM24PEVLK Инструкция по эксплуатации
- Daikin FDM30PEVLK Инструкция по эксплуатации
- Daikin FDM36PEVLK Инструкция по эксплуатации
- Daikin FDM42PEVLK Инструкция по эксплуатации
- Daikin FDM48PEVLK Инструкция по эксплуатации
- Daikin FDYM24PEVLK Инструкция по эксплуатации
- Daikin FDYM30PEVLK Инструкция по эксплуатации
- Daikin FDYM36PEVLK Инструкция по эксплуатации
- Daikin FDYM42PEVLK Инструкция по эксплуатации
- Daikin FDYM48PEVLK Инструкция по эксплуатации
- Daikin R24PEVLK Инструкция по эксплуатации
- Daikin R30PEVLK Инструкция по эксплуатации
- Daikin R36PEVLK Инструкция по эксплуатации
- Daikin R42PETLK Инструкция по эксплуатации
- Daikin R42PEYLK Инструкция по эксплуатации
- Daikin R48PETLK Инструкция по эксплуатации
- Daikin R48PEYLK Инструкция по эксплуатации
- Daikin RY24PEVLK Инструкция по эксплуатации
- Daikin RY30PEVLK Инструкция по эксплуатации