Daikin EKHY075787 [4/4] Ekhy075787 ekps075867 ekps075877 ekps075917 ekps076197 ekps 076207 ekps076217 ekps076227
![Daikin EKPS075917 [4/4] Ekhy075787 ekps075867 ekps075877 ekps075917 ekps076197 ekps 076207 ekps076217 ekps076227](/views2/1798439/page4/bg4.png)
EKHY075787 / EKPS075867 / EKPS075877 / EKPS075917
EKPS076197 / EKPS 076207 / EKPS076217 / EKPS076227
Conversion Instructions
1. Remove the cover cap (A) on the gas valve so setting screw B will become
accessible.
2. Activate the test program for minimum output by simultaneously pressing
the buttons and . A capital L appears in the service display.
3. Wait until the reading of the analyser is stabilized (min. 3 minutes).
4. Measure the O2(L) or CO2(L) value.
5. Set the correct value for O2(L) or CO2(L) by turning setting screw B.
See table 4 or 5 for the correct value.
Choose the correct table. Table 4 is for Propane, table 5 is for
Natural Gas G25.
(CO2(H) is the value that has been noted during the measurement
on maximum output.
Turning the adjustment screw clockwise will raise the CO
2
value.
Turning anti clockwise will lower the CO
2
value.
Change the setting in small steps and wait until the reading is
stabilized before continuing.
Table 4: Determining the correct setting of CO
2
at minimum output for propane
G31 (front panel removed)
Propane 3P G31 (30 & 50 mBar)
Measured value am maximim power
(See § 3.1)
Prescribed value at minimum power
(= CO
2
(H) – 0.3)
CO
2
(H) [%]
CO
2
(L) [%]
10.8
10.5 ±0.1
10.6
10.3 ±0.1
10.4
10.1 ±0.1
10.2
9.9 ±0.1
10.0
9.7 ±0.1
9.8
9.5 ±0.1
Table 5: Determining the correct setting of CO
2
at minimum output for natural
gas G25 (front panel removed)
Natural gas G25 (25 mBar)
Measured value am maximim power
(See § 3.1 )
Prescribed value at minimum power
(= 0.5 x CO
2
(H) + 4.2)
CO
2
(H) [%]
CO
2
(L) [%]
9.6
9.0 ±0.1
9.4
8.9 ±0.1
9.2
8.8 ±0.1
9.0
8.7 ±0.1
8.8
8.6 ±0.1
8.6
8.5 ±0.1
6. Reposition the cover cap A of the setting screw B for protection.
7. Repeat the measurement at maximum output (§ 3.1) to ensure the correct
operation of the boiler.
8. Place the front panel back on the boiler.
9. Activate the test program for maximum output by simultaneously pressing the
buttons and twice. A capital H appears in service display.
10. Check the CO value of the combustion to make sure no recirculation is taking
place.
11. Switch the appliance off with the button. [-] is shown in the service display.
12. Remove the measuring probe and reposition the cap X on the sampling point off
the adapter.
13. Switch the appliance on with the button .
14. Check if the central heating and (when available) DHW are working properly.
88508702
Achterzijde ventilator met geïntegreerde
tunnelventuri.
Achterzijde ventilator met geïntegreerde
tunnelventuri.
Содержание
- Boiler configuration 1
- Ekhy075787 ekps075867 ekps075877 ekps075917 ekps076197 ekps 076207 ekps076217 ekps076227 1
- Another gas type the c 2
- Caution checking the c 2
- Conversion of the gas ring 2
- During the check the installation location must not be under the 2
- Ekhy075787 ekps075867 ekps075877 ekps075917 ekps076197 ekps 076207 ekps076217 ekps076227 2
- Front panel removed 2
- Influence of over or under pressure situations 2
- It is not possible to adjust the c 2
- Prescribed range the boiler has to be checked on gas tightness and usage of the correct components in particular the gas ring the insert and the fan 2
- Setting needs to be checked 2
- Setting of the boiler must be executed with the 2
- The maximum deviation of the flue gas analyser that is allowed is 2
- Value at maximum power when the value measured at maximum power falls without the 2
- When replacing parts that can affect combustion or conversion to 2
- Checking and adjusting c 3
- Ekhy075787 ekps075867 ekps075877 ekps075917 ekps076197 ekps 076207 ekps076217 ekps076227 3
- Setting 3
- Ekhy075787 ekps075867 ekps075877 ekps075917 ekps076197 ekps 076207 ekps076217 ekps076227 4
Похожие устройства
- Daikin EKHY075787 Брошюра
- Daikin EKPS075867 Инструкция по монтажу
- Daikin EKPS075867 Брошюра
- Daikin EKPS075877 Инструкция по монтажу
- Daikin EKPS075877 Брошюра
- Daikin EKPS075917 Инструкция по монтажу
- Daikin EKPS075917 Брошюра
- Daikin EKPS076197 Инструкция по монтажу
- Daikin EKPS076197 Брошюра
- Daikin EKPS076207 Инструкция по монтажу
- Daikin EKPS076207 Брошюра
- Daikin EKPS076217 Инструкция по монтажу
- Daikin EKPS076217 Брошюра
- Daikin EKPS076227 Инструкция по монтажу
- Daikin EKPS076227 Брошюра
- Daikin EKTH3 Инструкция по монтажу
- Daikin EKTH3 Брошюра
- Daikin EKTH4 Инструкция по монтажу
- Daikin EKTH4 Брошюра
- Daikin EVLQ05CAV3 Инструкция по монтажу