7.4 Periodic checks
Carry out periodic checks to make sure the unit is working correctly:
OPERATION
RECOMMENDED
FREQUENCY
Checktheoperationofallthecontrolandsafetyequipmentasdescribedpreviously. Monthly
Check the tightness of the electrical terminals in the electrical control panel and in the terminal
boardsofthecompressors.Themovingandxedcontactsofthecontactorsmustbecleaned
periodically and should be replaced whenever they show signs of deterioration.
Monthly
Checktherefrigerantchargethroughtheliquidsightglass. Monthly
Make sure there are no oil leaks from the compressor. Monthly
Check the crankcase heaters of the compressors. Monthly
Cleanthennedcoilbyfollowingtheinstructionsinthe“Externalcleaning”sectionaccording
to the type of coil installed
Monthly
Cleantheairlters Monthly
Cleantheventilationltersoftheelectricalcontrolpanel. Monthly
Carry out the defrosting test. Monthly
Checkthemoistureindicatorontheliquidsightglass(green=dry,yellow=wet).Ifthe
indicatorisnotgreen,asindicatedonthesightglasssticker,replacethelter.
4 months
Checkthecondition,xingandbalanceofthefans. 4 months
Check that the noise emitted by the unit is normal. 4 months
This planning refers to an average installation; there could be installations in which it may be
necessarytoincreasethefrequencyofsomechecks.
Currentlegislationmayrequirelongerintervalsonperiodicchecksthantherecommendedones,also
with reference to the installed safety devices and the refrigerant charge present, without voiding the
warranty on the unit.