Translation from original instructions
Installation manual
40
We reserve the right to make changes without any prior notice.
UATYQ*Y1
Packaged Rooftop
4P522680-1
7.5 Unscheduled maintenance
After correctly starting-up and carrying out the relevant checks, the units normally do not need any intervention by the
customer service in order to check the charge of the refrigerant gas.
7.5.1 Special work
Over time, small leaks allowing the refrigerant gas to escape could be generated, so partially draining the circuit and
causing malfunctioning of the unit.
In these cases, the points from which the refrigerant gas is escaping must be found. These must be repaired and the
chargemustberestored,workingincompliancewithcurrentrulesandregulationsregardingequipmentcontaining
uorinatedgreenhousegases.
7.5.2 Exceptional work
Withuseoftheunit,particularsituationsmayoccurthatrequireworktobecarriedoutpromptly.
Even in an emergency, work on the unit must be carried out by skilled personnel in safe conditions.
The presence of oil on the unit, on the pipes or on parts of the unit can be a sign of gas leaks.
Repair the leakage point and restore the charge of refrigerant gas.
In the case of small oil leaks, clean the dirty parts with absorbent cloths, otherwise recover the leaked oil with absorbent
sheets. In any case, the material used must be disposed of in accordance with current rules and regulations.
Check whether it is necessary to restore the oil charge.
Содержание
- Installation use and maintenance manual 1
- Models 1
- Rooftop packaged unit 1
- Rooftop packaged unit english 1
- Contents 3
- Installation 22 3
- Introduction 6 3
- Product description 16 3
- Receiving the product and storage 13 3
- Safety 8 3
- Commissioning 30 4
- Decommissioning 41 4
- Maintenance 36 4
- Conformity 6
- Description 6
- Introduction 6
- Symbols 6
- Labels 7
- General safety precautions 8
- Safety 8
- Discharge of the safety valves 9
- Basic rules 10
- Noise levels 11
- Residual risks 11
- Hazards and health consequences 12
- Safetyinformationontherefrigerantfluid 12
- Handling 13
- Receiving the product and storage 13
- Reception 13
- Transport 13
- Storage 15
- Intended use 16
- Product description 16
- Unintended use 16
- Control and safety devices 17
- Principles of operation 17
- Specifications 17
- Structure 17
- Air system 18
- Airflowsensor 18
- Flow rate sensor for fans 18
- Internal air fans 18
- Airfiltersg4 19
- Dirtyfiltersensor 19
- Programmable control 20
- Wiring diagram 21
- Dimensions and weight 22
- Installation 22
- Installation site 22
- Fitting of rain hoods 23
- Installation 23
- Anti vibration mounts 24
- External positioning 24
- Minimum distances 25
- Electrical connections 26
- Condensate drain connections 28
- Condensate drain of the external air coil 28
- Condensate drain of the internal air coil 28
- Aeraulic connections 29
- Connection of the ducts 29
- Return and supply ducts 29
- Commissioning 30
- Preliminary operations 30
- First starting 31
- Functional tests 31
- Preliminary checks 31
- Calibration of safety components 32
- Control and safety components unit activation set 32
- Point differential reset 32
- Checks during operation 33
- Alarms and malfunctions 34
- Symptom likely cause possible solution 34
- Stop for long periods of time 35
- Temporary stop 35
- Adjustments 36
- Maintenance 36
- Cleaning the coils 37
- External cleaning 37
- Cleaning the unit 38
- Internal cleaning 38
- Periodic checks 39
- Exceptional work 40
- Special work 40
- Unscheduled maintenance 40
- Decommissioning 41
- P522680 44
- Um_dkn_0001_rooftop_en_12 09 2018_rev02 44
Похожие устройства
- Daikin UATYQ75ABAY1 Инструкция по эксплуатации
- Daikin UATYQ75ABAY1 Инструкция по монтажу
- Daikin UATYQ90ABAY1 Инструкция по эксплуатации
- Daikin UATYQ90ABAY1 Инструкция по монтажу
- Apeyron Electrics 03-58 Инструкция по эксплуатации
- Daikin UATYQ100ABAY1 Инструкция по эксплуатации
- Daikin UATYQ100ABAY1 Инструкция по монтажу
- Daikin UATYQ115ABAY1 Инструкция по эксплуатации
- Daikin UATYQ115ABAY1 Инструкция по монтажу
- Daikin UATYQ20AFC2Y1 Инструкция по эксплуатации
- Daikin UATYQ20AFC2Y1 Инструкция по монтажу
- Apeyron Electrics 03-59 Инструкция по эксплуатации
- Daikin UATYQ25AFC2Y1 Инструкция по эксплуатации
- Daikin UATYQ25AFC2Y1 Инструкция по монтажу
- Apeyron Electrics 03-60 Инструкция по эксплуатации
- Apeyron Electrics 03-68 Инструкция по эксплуатации
- Apeyron Electrics 03-69 Инструкция по эксплуатации
- Apeyron Electrics 03-71 Инструкция по эксплуатации
- Apeyron Electrics 03-72 Инструкция по эксплуатации
- Comet BWD-K 2527 G (9,8/186); 3400 об/мин.3/4” п.в. Инструкция по эксплуатации