Daikin LRYEN10A7Y1 [9/44] Maintenance and service
![Daikin LRYEN10A7Y1 [9/44] Maintenance and service](/views2/1801918/page9/bg9.png)
6 Maintenance and service
Installation and operation manual
9
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit and capacity up unit
4P605461-1B – 2020.08
Side Design pressure
Refrigeration 90bar
Air conditioning 120bar
6 Maintenance and service
NOTICE
Never inspect or service the unit by yourself. Ask a
qualified service person to perform this work.
WARNING
Never replace a fuse with a fuse of a wrong ampere ratings
or other wires when a fuse blows out. Use of wire or
copper wire may cause the unit to break down or cause a
fire.
CAUTION
Do NOT insert fingers, rods or other objects into the air
inlet or outlet. Do NOT remove the fan guard. When the
fan is rotating at high speed, it will cause injury.
CAUTION
After a long use, check the unit stand and fitting for
damage. If damaged, the unit may fall and result in injury.
NOTICE
Do NOT wipe the controller operation panel with benzine,
thinner, chemical dust cloth, etc. The panel may get
discoloured or the coating peeled off. If it is heavily dirty,
soak a cloth in water-diluted neutral detergent, squeeze it
well and wipe the panel clean. Wipe it with another dry
cloth.
6.1 About the refrigerant
This product contains refrigerant gases.
Refrigerant type: R744 (CO
2
)
WARNING
▪ Do NOT pierce or burn refrigerant cycle parts.
▪ Do NOT use cleaning materials other than those
recommended by the manufacturer.
▪ Be aware that the refrigerant inside the system is
odourless.
WARNING
The R744 refrigerant (CO
2
) inside the unit is odourless,
non-flammable and normally does NOT leak.
If the refrigerant leaks in high concentrations in the room, it
may have negative effects on its occupants such as
asphyxiation and carbon dioxide poisoning. Ventilate the
room and contact the dealer where you purchased the unit.
Do NOT use the unit until a service person confirms that
the part from which the refrigerant leaked has been
repaired.
6.2 Recommended maintenance and
inspection
Since dust collects when using the unit for several years,
performance of the unit will deteriorate to some extent. As taking
apart and cleaning interiors of units requires technical expertise and
in order to ensure the best possible maintenance of your units, we
recommend to enter into a maintenance and inspection contract on
top of normal maintenance activities. Our network of dealers has
access to a permanent stock of essential components in order to
keep your unit in operation as long as possible. Contact your dealer
for more information.
When asking your dealer for an intervention, always state:
▪ The complete model name of the unit.
▪ The manufacturing number (stated on the nameplate of the unit).
▪ The installation date.
▪ The symptoms or malfunction, and details of the defect.
WARNING
▪ Do NOT modify, disassemble, remove, reinstall or
repair the unit yourself as incorrect dismantling or
installation may cause an electric shock or fire. Contact
your dealer.
▪ In case of accidental refrigerant leaks, make sure there
are no naked flames. The refrigerant itself is entirely
safe, non-toxic and non-combustible, but it will
generate toxic gas when it accidentally leaks into a
room where combustible air from fan heaters, gas
cookers, etc. is present. Always have qualified service
personnel confirm that the point of leakage has been
repaired or corrected before resuming operation.
7 Troubleshooting
If system malfunctions are likely to degrade the articles in the room/
showcase, you can ask your installer to install an alarm (example:
lamp). For more information, contact your installer.
If one of the following malfunctions occur, take the measures shown
below and contact your dealer.
WARNING
Stop operation and shut off the power if anything
unusual occurs (burning smells etc.).
Leaving the unit running under such circumstances may
cause breakage, electric shock or fire. Contact your dealer.
The system MUST be repaired by a qualified service person.
Malfunction Measure
If a safety device such as a fuse, a
breaker or an earth leakage breaker
frequently actuates or the ON/OFF
switch does NOT properly work.
Turn OFF the main power
switch.
If water leaks from the unit. Stop the operation.
The operation switch does NOT work
well.
Turn OFF the power
supply.
If the user interface display indicates the
unit number, the operation lamp flashes
and the malfunction code appears.
Notify your installer and
report the malfunction
code.
If the system does NOT operate properly except for the above
mentioned cases and none of the above mentioned malfunctions is
evident, investigate the system in accordance with the following
procedures.
If after checking all above items, it is impossible to fix the problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).
Содержание
- Co ₂ conveni pack outdoor unit and capacity up unit 1
- Installation and operation manual 1
- Lryen10a7y1 lrnun5a7y1 1
- B1 b2 b3 2
- C1 c2 c3 2
- Installation and operation manual 2
- About the box 10 3
- About the documentation 3
- About the documentation 3 3
- About the system 8 3
- About the units and options 11 3
- About this document 3
- Authorised installers end users 3
- Charging refrigerant 31 3
- Commissioning 34 3
- Configuration 33 3
- Disposal 10 3
- Electrical installation 25 3
- For the installer 10 3
- For the user 5 3
- Maintenance and service 9 3
- Operation 8 3
- Piping installation 17 3
- Relocation 10 3
- Specific installer safety instructions 4 3
- Table of contents 3
- Target audience 3
- Technical data 40 3
- Troubleshooting 37 3
- Troubleshooting 9 3
- Unit installation 13 3
- User safety instructions 5 3
- Specific installer safety instructions 4
- For the user 5
- User safety instructions 5
- General 6
- Instructions for safe operation 6
- About the system 8
- Design pressure 8
- Do not use the unit until a service person confirms that the part from which the refrigerant leaked has been repaired 8
- If the refrigerant leaks in high concentrations in the room it may have negative effects on its occupants such as asphyxiation and carbon dioxide poisoning ventilate the room and contact the dealer where you purchased the unit 8
- Inside the unit is odourless non flammable and normally does not leak 8
- Leaving the unit running under such circumstances may cause breakage electric shock or fire contact your dealer 8
- Operation 8
- Operation range 8
- Stop operation and shut off the power if anything unusual occurs burning smells etc 8
- System layout 8
- The r744 refrigerant c 8
- Warning 8
- About the refrigerant 9
- Maintenance and service 9
- Recommended maintenance and inspection 9
- Troubleshooting 9
- About the box 10
- Disposal 10
- Error codes overview 10
- For the installer 10
- Outdoor unit 10
- Relocation 10
- To handle the outdoor unit 10
- To unpack the outdoor unit 10
- About the outdoor unit 11
- About the units and options 11
- To remove the accessories from the outdoor unit 11
- About the units and options 12
- Labels on outdoor unit 12
- System layout 12
- Warning 12
- Additional installation site requirements for co ₂ refrigerant 13
- Additional installation site requirements for co₂ refrigerant 13
- Additional installation site requirements of the outdoor unit in cold climates 13
- Indoor unit constraints 13
- Installation site requirements of the outdoor unit 13
- Preparing the installation site 13
- Unit installation 13
- Appropriate measures 14
- Opening and closing the unit 14
- To determine the minimum number of appropriate measures 14
- To open the outdoor unit 14
- Unit installation 14
- To close the outdoor unit 15
- To open the electrical component box of the outdoor unit 15
- Unit installation 15
- Mounting the outdoor unit 16
- To provide the installation structure 16
- Unit installation 16
- Piping installation 17
- Preparing refrigerant piping 17
- Refrigerant piping material 17
- Refrigerant piping requirements 17
- To install the outdoor unit 17
- To provide drainage 17
- Piping installation 18
- Refrigerant piping length and height difference 18
- To select the piping size 18
- Piping installation 19
- Piping size between branching areas or between first and second branch 19
- Piping size between outdoor unit and first branch 19
- Piping size from branch to indoor unit 19
- Piping installation 20
- Stop valve size 20
- To close the stop valve 20
- To handle the stop valve 20
- To open the stop valve 20
- To select expansion valves for refrigeration 20
- To select refrigerant branch kits 20
- Using stop valves and service ports 20
- Piping installation 21
- Tightening torques 21
- To close the service port 21
- To handle the service port 21
- To open the service port 21
- Connecting the refrigerant piping 22
- Piping installation 22
- To connect the refrigerant piping to the outdoor unit 22
- To remove the spun pipes 22
- Guidelines to connect t joints 23
- Guidelines to install a dryer 23
- Guidelines to install safety valves 23
- Piping installation 23
- Checking refrigerant piping setup 24
- Checking the refrigerant piping 24
- Insulating the refrigerant piping 24
- Piping installation 24
- To perform a leak test 24
- To perform vacuum drying 24
- About electrical compliance 25
- Electrical installation 25
- Electrical installation 26
- Field wiring overview 26
- Electrical installation 27
- Guidelines when connecting the electrical wiring 27
- Guidelines when knocking out knockout holes 27
- Specifications of standard wiring components 27
- Connections to the outdoor unit 28
- Electrical installation 28
- Low voltage wiring outdoor unit 28
- Connections to the capacity up unit 29
- Electrical installation 29
- High voltage wiring outdoor unit 29
- Electrical installation 30
- High voltage wiring capacity up unit 30
- Low voltage wiring capacity up unit 30
- Charging refrigerant 31
- Precautions when charging refrigerant 31
- Charging refrigerant 32
- To charge refrigerant 32
- To determine additional refrigerant amount 32
- About making field settings 33
- Configuration 33
- Field setting components 33
- Making field settings 33
- To access mode 1 or 2 33
- To access the field setting components 33
- Bs1 5 s 34
- Checklist before commissioning 34
- Commissioning 34
- Precautions when commissioning 34
- About the test run 35
- Commissioning 35
- Test run checks 35
- To perform a test run 7 segment display 35
- Bs1 bs2 bs3 36
- Commissioning 36
- Correcting after abnormal completion of the test run 36
- Logbook 36
- Error codes overview 37
- Solving problems based on error codes 37
- Troubleshooting 37
- Troubleshooting 38
- Troubleshooting 39
- A subset of the latest technical data is available on the regional daikin website publicly accessible the full set of latest technical data is available on the daikin business portal authentication required 40
- Piping diagram outdoor unit 40
- Technical data 40
- Piping diagram capacity up unit 41
- Technical data 41
- Technical data 42
- Wiring diagram outdoor unit 42
- Technical data 43
Похожие устройства
- Daikin LRYEN10A7Y1 Справочное руководство для монтажника
- Daikin LRYEQ16A7Y1 Инструкция по эксплуатации
- Daikin LRYEQ16A7Y1 Брошюра
- Daikin LRLEQ3BY1 Технические данные
- Daikin LRLEQ3BY1 Общие правила техники безопасности
- Daikin LRLEQ3BY1 Инструкция по эксплуатации
- Daikin LRLEQ3BY1 Руководство по применению для установщика
- Daikin LRLEQ4BY1 Технические данные
- Daikin LRLEQ4BY1 Общие правила техники безопасности
- Daikin LRLEQ4BY1 Инструкция по эксплуатации
- Daikin LRLEQ4BY1 Руководство по применению для установщика
- Daikin LRLEQ5AY1 Справочное руководство для монтажника
- Daikin LRLEQ5AY1 Сервис мануал
- Daikin LRLEQ5AY1 Инструкция по эксплуатации
- Daikin LRLEQ5AY1 Инструкция по монтажу
- Daikin LRLEQ5AY1E Справочное руководство для монтажника
- Daikin LRLEQ5AY1E Сервис мануал
- Daikin LRLEQ5AY1E Инструкция по эксплуатации
- Daikin LRLEQ5AY1E Инструкция по монтажу
- Daikin LRLEQ6AY1 Справочное руководство для монтажника