Daikin LRYEQ16A7Y1 [11/96] Daikin refrigeration product portfolio and ecodesign directive

Daikin LRYEQ16A7Y1 [11/96] Daikin refrigeration product portfolio and ecodesign directive
11
COP methodology:
If the medium temperature cooling capacity is
lower thаn 5 kW and low temperature cooling
capacity is lower than 2 KW
COP given on 25°C ambient temperature
COP given on 32°C ambient temperature
COP given on 43°C: mandatory if ambient
temperature design is higher or equal to 35°C
Two methodologies to evaluate the unit performance
Minimum eciency (COP):
Medium temperature:
Capacity lower or equal 1 kW = 1.2
Capacity lower or equal 5 kW = 1.4
Low temperature:
Capacity lower or equal 1 kW = 0.75
Capacity lower or equal 2 kW = 0.85
SEPR methodology:
If the medium temperature cooling capacity is
between 5kW and 50kW and low temperature
cooling capacity is between 2kW and 20kW
SEPR given on the reference climate zone of
Strasbourg
COP given on 43°C: mandatory if ambient
temperature design is higher or equal to 35°C
Minimum eciency (SEPR):
Medium temperature:
Capacity lower or equal 20 kW = 2.25
Capacity lower or equal 50 kW = 2.35
Low temperature:
Capacity lower or equal 8 kW = 1.5
Capacity lower or equal 20 kW = 1.6
Low capacities
Condensing unit installed indoor
Higher capacities
Condensing unit installed outdoors
(climate depending)
Model
MONOBLOCKS
BIBLOCKS
WINEBLOCKS
JEHCCU
JEHSCU
MINI ZEAS ZEAS MULTI ZEAS CONVENI-PACK BOOSTER
OTHER RANGES
Refrigerating
capacity <20kw
Refrigerating
capacity <50kw
Refrigerating
Capacity >50kW
Medium
temperature
(Te = -10°C)
out of scope in scope in scope in scope
out of
scope
(1)
out of
scope
(2)
- in scope in scope out of scope
Low
temperature
(Te = -35°C)
out of scope in scope in scope in scope
out of
scope
(1)
- out of scope
(3)
in scope out of scope out of scope
() Delivered capacity of the multi Zeas units in medium and low temperature application are higher than the upper boundary (MT: Q >  kW; LT: Q >  kW) mentioned in the Ecodesign
Directive
() The CVP can only operates when also Daikin indoor units are connected. This means that the CVP can be seen as a condensing unit with multiple condensers which is considered out of
scope of the Ecodesign Directive ENTR LOT
() The booster unit is not seen as a condensing unit, because the heat extracted from the evaporator side is (LT –side) discharge in the MT refrigerant line of a CVP or Zeas unit and not to
the surrounding air as described in the Ecodesign Directive ENTR LOT
Daikin refrigeration product portfolio and Ecodesign Directive