Daikin LRYEQ16A7Y1 [78/96] Pattern 1 pattern 1

Daikin LRYEQ16A7Y1 [78/96] Pattern 1 pattern 1
Integrated solutions
78
Detailed technical drawings
LRYEQ16AY
LRYEQ-AY
1.
Heights of walls in case of patterns 1 and 2:
Front: 1500
Suction side: 500mm
Side: Height unrestricted
The installation space as shown on this drawing is based on cooling operation at 32°C (outdoor air temperature).
If the design outdoor air temperature exceeds 32°C degrees, provide a broader suction space than showing on the drawing.
2. If the walls are higher than mentioned above, then additional space is needed.
Suction side: service space + h2/2
Front side: service space + h1/2
See figure 1
3. When installing the units, select the pattern that best fits the available space.
Always keep in mind to leave sufficient space for a person to pass between unit and wall and for the air to circulate freely.
If more units are to be installed than are catered for in the above patterns, your layout should take into account of the
possibility of short circuits).
4. Provide sufficient space at the front to connect refrigerant piping (comfortably).
For single unit installation
Pattern 1 Pattern 1
Pattern 2Pattern 2
Pattern 2
Pattern 3Pattern 3
Pattern 1
10 or more
300 or more 300 or more
100 or more100 or more
100 or more 100 or more
500 or more
500 or more
300 or more300 or more
400 or more400 or more
200 or more
200 or more
50 or more
50 or more
50 or more
50 or more
500 or more500 or more
300 or more
300 or more
300 or more
600 or more
20 or more
20 or more
500 or more
20 or more
20 or more
500 or more
500 or more
50 or more
50 or more
50 or more
50 or more
500 or more
100 or more
100 or more 100 or more
100 or more
50 or more 50 or more
50 or more
50 or more
100 or more
100 or more
100 or more
500 or more
10 or more 10 or more 20 or more 20 or more 10 or more
10 or more
10 or more
10 or more 10 or more
10 or more
10 or more
10 or more 10 or more
For installation in rows For centralized group layout
suction side
front side
front
front
front
front
front
front
front
front front
front
front
front
front
front
Wall height unrestricted
Wall height unrestricted
Figure 1
3D106211
LRYEQ-AY
3D066895A
LRYEQ16AY
(Knock-out hole)
(Knock-out hole)
1 Liquid (For air conditioner)
ø
9.5 Brazed connection
2 Gas (For air conditioner)
ø 25.4 Brazed connection
3 Gas (For refrigeration)
ø 25.4 Brazed connection
4 Liquid (For refrigeration)
ø 9.5 Brazed connection
5 Grounding terminal inside of switch box (M8)
6 Power cord routing hole (side)
ø 62
7 Power cord routing hole (front)
ø 45
8 Power cord routing hole (front)
ø 27
9 Power cord routing hole (bottom)
ø 50
10 Wire routing hole (front)
ø 27
11 Pipe routing hole (front)
12 Pipe routing hole (bottom)
(Knock-out hole)
(Knock-out hole)
Detail for bottom side
Detail for front side
(Pitch of foundation bolt holes)
(foundation bolt hole)
4-15X22,5-mm-Oblong holes
(Pitch of foundation bolt holes)
Detail A
Detail A