Daikin LRYEQ16A7Y1 — много компрессорные конденсаторные установки для охлаждения [44/96]

Daikin LRYEQ16A7Y1 [44/96] The refrigeration system is fitted with
Condensing units
44
Multi compressor condensing
unit with semi hermetic
compressors
General features:
Capacity for MT cooling:  kW to  kW
Capacity for LT cooling:  kW to  kW
Ambient temperature range : - °C - +°C
RA a, R A, RA, RA RF
Compressors:
- LHB*: Bitzer
- LHD* : Dorin
- LHR* : Frascold
- LHC* : Stream
Other types, brands and capacities are possible on request
Conditions:
MT: Ambient temperature: °C Evp. Temperature: -°C
LT: Ambient temperature: °C Evp. Temperature: -°C
LHB, LHD, LHR and LHC
General description:
Basic Frame Version:
Basic frame made from folded and painted steel
sheet, screwed with bolts to make a basic structure to
fix the components on it.
Basic Refrigerating System:
The compressors (3 or 4) are connected in parallel,
with only one suction and discharge header. Each
compressor is fitted with shut-off valves on suction
line and discharge line.
The compressors are fixed to the frame through
rubber anti-vibration supports.
Compressors used for low temperature are complete
with fan heads.
The oil equalization system is composed of an
oil separator and an equalization header, which
are mounted on the compressor oil sight glass
connection.
According to the number of compressors fitted, there
is one or two oil level indicator/s, fitted onto the
equalization header.
The refrigerating system is equipped with liquid
receivers, if there is more than one receiver, the
installation is made in parallel with a safety valve, a
dehydration cartridge filter, interchangeable, liquid
level alarm, liquid sight glass and shut-off valves.
On suction line there is a mechanical cartridge filter,
interchangeable.
The refrigeration system is fitted with:
General high pressure switch, adjustable and
autoresetting
General low pressure switch, adjustable and
autoresetting
Oil pressure switch for each compressor
Emergency low pressure switch, adjustable and
autoresetting
Low pressure switches for each compressor
emergency, adjustable and autoresetting
Electronic speed regulator for condenser fan with
pressure probe for three phase fans and with
temperature probe for mono phase fans + bypass
Low pressure probe, placed on suction header for
capacity control
High pressure gauge
Low pressure gauge
Electrical panel:
Standard power distribution
Disconnecting switch
Compressors protection, with overload cut-out motor
protector; fuses for fans protection, thermos contacts
for each single fan
Auxiliary circuit 230 volt through transformer
400V/230V
Electronic card XC440C
IP55 with greed and ventilation fan
On the door there is the electronic card and 4 lamps:
emergency (button + lamp), fans block, high pressure
switch block, low pressure
Switch block, and selector for on/off compressors