General-Fujitsu ASG30UBBJ [14/40] Abgg30lrta a abgg36lrta a abgg45lrta a

General-Fujitsu ARHA18LATN [14/40] Abgg30lrta a abgg36lrta a abgg45lrta a
064
CEILING
INVERTER
Specifications
Single
phase
For ABGG30/36LRTA-AWired R.C. For ABGG45LRTA-A
Model : ABGG30LRTA-A / ABGG36LRTA-A / ABGG45LRTA-A
Capacity
EER
COP
Running Current
Moisture Removal
Airflow Rate (High)
Sound Pressure
Net Dimension H
x
W
x
D
Net Weight
Piping Connections (Small / Large)
Max Height Difference
Operation Range
Cooling
Heating
Drain Pipe Diameter (I.D./O.D.)
Max Pipe Length (Pre-Charge)
Refrigerant
Heating
Cooling/HeatingInput Power
Power Source
Cooling
Cooling
Indoor
Outdoor
Indoor (High)
Outdoor
Heating
Cooling/Heating
Indoor
Outdoor
°CDB
mm
m
kg(lbs)
mm
kW
kg(lbs)
A
W/W
m
3
/h
I/h
dB(A)
mm
V/ Ø/Hz
kW
BTU/h
kW
BTU/h
Model No.
Indoor unit
Outdoor unit
230/1/50
8.50
29,000
10.00
34,100
2.54/2.77
3.35
3.61
11.1/12.2
2.5
45
53
1,660
3,600
240×1660×700
46.0(101)
830x900x330
61.0(135)
9.52/15.88
22.0/25.6
50(20)
30
-15 to 46
-15 to 24
R410A
230/1/50
9.40
32,100
11.20
38,200
2.93/3.02
3.21
3.71
12.8/13.2
3.0
47
55
1,900
3,800
240×1660×700
46.0(101)
830x900x330
61.0(135)
9.52/15.88
22.0/25.6
50(20)
30
-15 to 46
-15 to 24
R410A
230/1/50
12.10
41,300
13.30
45,400
3.77/3.68
3.21
3.61
16.4/16.1
4.0
49
55
2,100
6,750
240×1660×700
46.0(101)
1290×900×330
88.0(194)
9.52/15.88
22.0/25.6
50(20)
30
-15 to 46
-15 to 24
R410A
Installation Multi auto swing
A combination of right/left and up/down directional swing
allows 3-dimensional air direction control.
Steps
Swing: Cooling , Dry and Fan mode
Swing: Heating and Fan mode
Right and Left Swing Up and Down Swing
5 steps selectable 5 steps selectable
1
2
5
4
3
1
2
5
4
3
(Field Supplied)
Open Concealed
Wall mounted
ABGG30LRTA-A
AOGG30LBTA-A
ABGG36LRTA-A
AOGG36LBTA-A
ABGG45LRTA-A
AOGG45LBTA-A
065
SPLIT / INVERTER
SplitSplit
Dimensions
Optional parts
Wired Remote Controller:
Simple Remote Controller:
Drain Pump Unit:
External Connect Kit:
External Control Set:
Flange:
UTY-RNNGM
UTY-RSNGM
UTR-DPB24T
UTY-XWZX
UTY-XWZXZ2
UTY-XWZXZ3
UTD-ECS5A
UTD-RF204
Models: (Unit : mm)
Refrigerant piping flare connection (Liquid)
Refrigerant piping flare connection (Gas)
Drain piping connection
2
1
3
1 32
3
Condensate lift-up mechanism (Option)
Optional drain lift-up
mechanism allows flexible
installation.
Fresh air intake
Outdoor
Indoor
Fresh
air
Max.
500mm
Easy installation
Main work settings can be done easily
from the remote controller
at installation
Setting by wireless or
wired remote controller
Conventional type
1
2
3
O
F
F
SW1
(Optional parts)
Setting by DIP switch inside control box
Main work settings
•High ceiling setting
•Auto restart
•Temperature adjustment when cooling / heating
Low noise mode of
outdoor unit (45/54 types)
2 stage low noise mode can be
selected.(Option)
Roted noise value
Mode 1
Mode 2
Low
noise
mode
-4dB-2dB
Low ambient operation
50
40
30
20
10
0
-10
-15°C
Cooling
24°C
Heating
46°C
-15°C
ABGG30LRTA-A / ABGG36LRTA-A / ABGG45LRTA-A

Содержание

Скачать