General-Fujitsu ASG30UBBJ [38/40] Power source

General-Fujitsu ARG9FUAB [38/40] Rear view
112
Specifications
Model : ARG25ALC / ARG30ALC / ARG36ALD3
[
3phase
]
/ ARG45ALC3
[
3phase
]
ARG25RLC / ARG30RLC / ARG36RLC3
[
3phase
]
/ ARG45RLC3
[
3phase
]
For ARG30ALC
ARG30RLC
Wired type
(With Weekly Timer)
For ARG25ALC
ARG25RLC
For ARG36/45ALC3
ARG36/45RLC3
Slim & Compact design
In the case of bottom return air connection, not only does
the indoor unit design allow for installation in a narrow
ceiling space of up to 270mm, Further space savings have
been achieved by mounting the electrical control box
internally inside the chassis.
1,135mm
1,200mm
270mm
Control box is now included as
part of the main chassis
One touch operating and easy to install
long life filter (Optional Parts)
Capacity
EER
COP
Running Current
Moisture Removal
Airflow Rate (High)
Net Dimension H
x
W
x
D
Net Weight
Piping Connections (Small / Large)
Max Height Difference
Operation Range
Cooling
Heating
Drain Pipe Diameter (I.D./O.D.)
Max Pipe Length (Pre-Charge)
Refrigerant
Heating
Cooling/HeatingInput Power
Power Source
Cooling
Cooling
Indoor
Heating
Cooling/Heating
Indoor
Outdoor
°CDB
mm
m
kg(lbs)
mm
kW
kg(lbs)
A
W/W
m
3
/h
I/h
mm
V/ Ø/Hz
kW
BTU/h
kW
BTU/h
Model No.
Indoor unit
Outdoor unit
ARG25ALC
AOG25ANBL
220-240/1/50
7.00-7.10
23,900-24,200
2.64-2.77 / —
2.65-2.56
13.00-13.00 / -
2.5
1,100
270x1,120x700
43.0 (95)
643x840x336
65.0 (143)
9.52/15.88
36.0/38.0
25(7.5)
15
21 to 43
R22
ARG30ALC
AOG30AMBH
220-240/1/50
8.60-8.80
29,400-30,000
3.30-3.40 / —
2.61-2.59
15.8-16.3 / -
4.0
1,750
270x1,120x700
43.0 (95)
900x900x350
79.0 (174)
9.52/15.88
36.0/38.0
30(7.5)
15
0 to 43
R22
ARG36ALD3
AOG36APA3L
380-415/3/50
10.30-10.50
35,200-36,000
3.90-4.00 / —
2.64-2.63
6.60-6.60 / -
3.1
2,000
270x1,120x700
45.0 (99)
1,152x940x370
94.0 (207)
9.52/19.05
36.0/38.0
50(10)
30
0 to 52
R22
ARG45ALC3
AOG45APA3L
380-415/3/50
12.40-12.70
42,500-43,500
4.50-4.57 / —
2.76-2.78
8.10-8.30 / -
6.0
2,200
270x1,120x700
45.0 (99)
1,152x940x370
102.0 (224)
9.52/19.05
36.0/38.0
50(20)
30
0 to 52
R22
ARG25RLC
AOG25RNBL
220-240/1/50
6.95-7.05
23,200-24,100
7.75-8.00
26,400-27,300
2.70-2.80 / 2.45-2.55
2.52-2.52
3.04-3.02
212.6-12.6/11.6-11.6
2.5
1,094
270x1,120x700
43.0 (95)
643x840x336
69.0 (152)
9.52/15.88
36.0/38.0
25(7.5)
15
0 to 43
-5 to 21
R22
ARG30RLC
AOG30RMBL
220-240/1/50
8.30-8.60
28,300-29,400
9.30-9.50
31,700-32,400
3.40-3.55 / 3.05-3.20
2.44-2.42
3.05-2.97
15.9-15.7 / 14.5-14.7
4.0
1,650
270x1,120x700
43.0 (95)
900x900x350
80.0 (176)
9.52/15.88
36.0/38.0
30(7.5)
15
0 to 43
-5 to 21
R22
ARG36RLC3
AOG36RPA3L
380-415/3/50
10.30-10.50
35,200-35,800
10.50-10.70
35,800-36,500
4.20-4.30 / 3.35-3.40
2.45-2.44
3.13-3.15
7.4-7.2 / 6.2-6.3
5.0
1,800
270x1,120x700
45.0 (99)
1,152x940x370
100.0 (220)
9.52/19.05
36.0/38.0
50(10)
30
0 to 52
-8 to 21
R22
ARG45RLC3
AOG45RPA3L
380-415/3/50
12.40-12.70
42,300-43,300
13.40-13.70
45,700-46,800
4.50-4.57 / 4.25-4.35
2.76-2.78
3.15-3.15
8.1-8.3 / 7.8-8.1
6.0
1,840
270x1,120x700
45.0 (99)
1,152x940x370
110.0 (243)
9.52/19.05
36.0/38.0
50(20)
30
0 to 52
-8 to 21
R22
MEDIUM STATIC PRESSURE DUCT
CONSTANT SPEED
113
SPLIT / CONSTANT SPEED
Easy maintenanceTwo-direction drain piping
Two-direction drain piping
Duct indoor unit
See below for the case of rear suction type
1.Control box
2.Fan casing
3.Fan
4.Motor
Previous model
2
4
1
3
Large bottom
panel: 1 piece
New model
1
4
3
2
Bottom panel:
2 pieces
Structural improvement is attained by making the bottom panel two pieces, front
and rear. The internal fan casing is also manufactured in two pieces, namely upper
and lower. The maintenance of the motor and fan can be easily carried out by
removing the rear panel and the lower part of the casing while leaving the main
chassis installed.
Installation styles
Embedded in Ceiling
Hanging from Ceiling
Optional parts
Simple Remote Controller: UTY-RSNGM
Flange: UTD-RF204 / UTD-SF045T
Drain Pump Unit: UTZ-PX1NBA
Long Life Filter: UTD-LF25NA
External Control Set: UTD-ECS5A
Dimensions
(Unit : mm)
Models: ARG25ALC / ARG30ALC / ARG36ALD3 / ARG45ALC3
ARG25RLC / ARG30RLC / ARG36RLC3 / ARG45RLC3
*Service accessibility must be allowed for when
installing the product.
Please consult the installation manual for the
necessary service access size.
Refrigerant piping flare connection (Liquid) :
Refrigerant piping flare connection (Gas) :
Drain piping connection (Drain pipe)
2
1
3
Rear view
Top view
Side view (R)
Side view (L)
Front view
240
270
107
1015
1135
173
161
447(Bolt pitch)
1177(Bolt pitch)
Outlet
270
32
ø200
(knock
out hole)
240
121
P.C.D. ø225
114
66
32
1
3
3
2
168
281
240
700
138
138
264 264 264
ø205 hole
82
75

Содержание

Скачать