Haier AU52NFIAKA [104/139] Resumeable heat

Haier AU52NFIAKA [104/139] Resumeable heat
Commercial Air Conditioner
Model: AU28/342FHAIA,
AU522FIAKA, AU52,60NFIAKA
-100-
gas pipe temp. sensor
indoor fan motor
fan
capacitor
CN14
3
2
1
4
CN13
3
6
5
4
7
2
1
10
8
9
1
2
4
3
B
A
5
4 3 2
6
7
1
10
9
7
8
2
3
1
4
6
5
liquid pipe temp. sensor
receive display
CN5
CN1
CN10
CN20
CN18
CN25
1PH.220-230V~.50Hz
Indoor unit wiring diagram
electronic
expansion valve
box power supply
and communication
R
R
CN1
2
1
ambient temp.
sensor
C D
2
1
wired controller
NOTE
Must connect electronic expansion valve box
power and communication from corresponding
indoor,wiring sequence must correspond with
the label respectively,other wise, will cause
PCB of indoor and electronic expansion valve
box not work and damaged.
M
electronic
expansion valve
CN6
42 3
1
5 6
2
3
1
CN11
float switch
1
3 2
negative ion generator or high
voltage accumulator
23
1 3 2
1
earthing
connector
pump motor
swing motor
CN19
CN22
only applicable for unit with
auxiliary electric heater
CN4
CN7
CN12
resumeable heat
protector70
10A/250VAC
auxiliary heater
FUSE
T15A/250VAC
About control board outer connector
indoor power
outdoor
communication
SW1
CN2
LED1LED2LED3
emergency switch(ON/OFF)
SW1
indicator power green
LED1
LED2
indicator timer yellow
indicator running red
LED3
B:Black
BL:Blue
BR:Brown
R:Red
W:White
Y/G:Yellow/Green
0010577030
2
1
choise of remote
cotroller type
choise of wire
controller type
water temperate sensor
Only used for inbuilt valve type
1
2
CN24
sw01
Indoor control board
unit code setting
sw03
sw02
CN16
serial
1
2
FUSE
T3.15A/250VAC
b
a
c
In the diagram,gas pipe temp. sensor,liquid pipe temp.
sensor,indoor fan motor are necessary parts;
Wired
expansion
are parts
(combined usage) .
Auxiliary electric
high voltage accumulator
comfort.
combination
Wired controller and receive display
only can choose one
The setting of SW01,SW02 and SW03 :
1.The former three bits of SW01 are used to set unit
number,which are operated by the installer on field .
2.The fourth bit of SW01 is used to choose different
indoor fan speed in heating mode."ON"means that fan
speed can be set as middle and low level,"OFF"means
that fan speed can be set as high,middle and low level.
3.The first bit of SW02 and SW03 is used to choose
wired control type or remote control type.
equipped with wired controller
can make remote
operation on wired controller with remote controller such
as YR-H71 .
"ON"means that the unit with wired controller(other parts
are as the same as remote control unit). And "OFF"is
remote controller.
4.The second bit of SW02 is used to choose built-in or
outside electronic expansion valve setting .
Attentions:
electronic expansion valve communication,and the
electronic expansion valve box(MP3A) control indoor
refrigerant flow.
CN6 is connected with
electronic expansion valve and indoor unit control
refrigerant flow itself.
CN25 is connected with
"OFF"means outside type:
"ON"means built-in type :
heater,negative ion generator,
are optional parts for health and
usage arbitrarily).
expansion valve setting .
outside electronic
Used for
E0
E1
E3
E4
E5
E9
E8
E7
E6
Float switch abnormal or water temperature sensor abnormal
Outdoor unit failure
Liquid pipe temperature sensor failure
Gas pipe temperature sensor failure
Repeated indoor unit number (E5 flashes for a while and then turn to E9)
EEPROM abnormal
Communication abnormal with EEV box
Communication abnormal between wired controller and indoor PCB
Communication abnormal between indoor and outdoor.
at will.
M
1.When the TES unit is used,the second bit of SW03 is
OFF and CN9 is connected with the water temp
.sensor ;otherwise ,the second bit of SW03 is ON and
without water temp.sensor .
2.The float switch and the water pump are optional in
the future .when the unit is with water pump,the float
switch should be connected or else should be short
connected with a jumper.
one-off heat protector
105 20A/250VAC
M
℃,
℃,
M
swing motor, indoor
controller,receive display,electronic
valve and
the model
Indoor temperate
sensor
temp. sensor
matched with
AE**2F A A wiring diagram: L I