Branch pipe selection:
1
2
3
4
1. The pipe between outdoor to the 1
st
branch pipe should be identical to the outdoor stop pipe. For
example, for AU60, liquid pipe is 12.7; gas pipe is 22.22.
2. The branch pipe should be selected as the indoor capacity:
capacity gas pipe liquid pipe branch pipe
9500
φ15.88 φ9.52 FQG-B120
9500
17900
φ19.05 φ9.52 FQG-B180
17900
φ22.22 φ12.7 FQG-B370
total capacity after the
indoor
3. The pipe between branch pipe should be confirmed as the total capacity of the indoors after the
branch pipe.
Total indoor capacity (100W
Gas pipe Liquid pipe
Φ15.88 Φ9.52
Φ19.05 Φ9.52
Φ22.22 Φ12.7
4. The pipe between branch pipe and indoor should be identical to the indoor pipe. But if the pipe is
more than30m from the 1
st
branch pipe, the gas pipe should be enlarged for a larger specification.
Commercial Air Conditioner
Model: AU28/342FHAIA,
AU522FIAKA, AU52,60NFIAKA
-27-
9.5
17.9
9.5
17.9