Haier AU52NFIAKA [95/139] Commercial air conditione

Haier AB142FCAIA [95/139] Commercial air conditione
11
Outdoor fan mode :_1low speed,_2med speed,_3high speed
12
Temperature sensor ON display ON
1OFF--
13
Four-way valve switched on: ON
1 Four-way valve not switched on: OFF_ _
14
Running mode selection cooling
C, heating: H
0
1
Dispatch line check cooling
CC --this function is preset
2
Dispatch line check heating
HH--this function is preset
3
Cool trial run
C --this function is preset
4 Heat trial run: H --this function is preset
5 Swing trial run: _F--this function is preset
6
Indoor unit uniform start/stop
run: 11/stop: 00
display -- after 3 minutes
--this function is preset
7 Clean abnormal function: CL--this function is preset
8
Outdoor PMV1fully openclose function: fully open: FF, fully close: 00
9
Outdoor PMV2 fully openclose function: fully open: FF, fully close: 00
10
Indoor PMV fully openclose functionfully open: FF
2
11 Outdoor rated setting: -F
0—7
Indoor communication state: receiving normal
1 receiving abnormal:
3
8 Display quantity of communicating indoor unit, e.g. : 6 shows that 6 indoor units
are working.
4 0—15 Indoor diagnosis code, no diagnosis code: --this function is preset
5 0—15 Indoor HP
new code:0 stands for 0.8HP, 1 stands for 1HP, 2 stands for 1.2HP,
3 stands for 1.5HP, 4 stands for 2HP, 5 stands for 2.5HP, 6 stands for 3HP, 7
stands for 4HP
Old code: 1 stands for 1HP,7 stands for 7HP
6 0—15 Indoor required capacity (decimalism) indoor P-CODE
7 0—15 Indoor PMV opening degree (decimalism)
8 0—15
Indoor saturation temperature (decimalism) -26.0—67.0account according to
outdoor suction pressure PS
9 1—16
Indoor sensor TA temperaturedecimalism-26.0—67.0
10 1—16
Indoor sensor TC2 temperatureindoor gas pipedecimalism-26.0—100.0
11 1—16
Indoor sensor TC1 temperatureindoor liquid pipedecimalism-26.0—100.0
12 1—16 Single cool trial run--this function is preset
13 1—16 Single heat trial run--this function is preset
Combination control with outdoor switches
Table 2
function summary Method of set, cancel
Cool trial run Indoor trial run in cooling
mode, the function is the
same as trial run with remote
controller, the indoor unit
which trials run fixes the temp.
difference as max. temp., and
send it to outdoor, the other
control is similar with normal.
[set]
SW01“2”, SW02“03”, press SW04 for more
than 2 seconds, after set of trial run success, LD
will always display –C until the function is
cancelled.
[cancel]
in trial run state, SW01“02”, SW02“03”, press
SW05
Heat trial run Indoor trial run in heating
mode, the function is the
same as trial run with remote
controller, the indoor unit
which trials run fixes the temp.
difference as max.
[set]
SW01“2”, SW02“04”, press SW04 for more than
4 seconds, after set of trial run success, LD will
always display –H until the function is cancelled.
[cancel]
in trial run state, SW01“02”, SW02“03”,
p
ress
Commercial Air Conditioner
Model: AU28/342FHAIA,
AU522FIAKA, AU52,60NFIAKA
-92-