Panasonic CS-F24DTE5 [40/150] Protection control

Panasonic CS-F43DTE5 / CU-B43DBE8 [40/150] Protection control
9.7.13. Pump-down Control
To enable pump down operation, at outdoor PCB, set the DS1and DS2 to OFF position.
Press Test Run button for 1 second.
During Pump Down operation, push the Test Run button again for 1 second to stop the pump down operation.
The pump down operation run for 10 minutes.
9.7.14. Thermostat Control
Depending on differences between room temperature and setting temperature, compressor operation is decided and starts
operation.
If temperature difference matches values shown below, thermostat switches off.
Cooling Mode -1.5°C
Soft Dry Mode -2.5°C
Heat Mode 3.5°C
9.8. Protection Control
9.8.1. Outdoor Low-pressure Protection Control
The purpose of low-pressure protection control is gas leakage detection control.
The low-pressure protection control starts when low-pressure switch is activated less than 15 minutes after compressor startup.
During heating operation or defrost control low-pressure detection does not start.
During this protection control, compressor is shut down, indoor unit is set to thermo-off status.
After 6 occasions, suction pressure error is displayed; all operation stopped except outdoor fan remaining heat removal control.
9.8.2. Outdoor High-pressure Protection Control
The high-pressure protection control starts when high-pressure switch is activated less than 15 minutes after compressor
startup.