Panasonic WH-SDF12C9E8 — устранение неисправностей передачи сигналов между блоками [80/125]

Panasonic WH-UD16CE8 [80/125] 0 indoor outdoor abnormal communication h90
80
16.5.10 Indoor/Outdoor Abnormal Communication (H90)
Malfunction Decision Conditions:
During operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is
checked whether it is normal.
Malfunction Caused:
1 Faulty outdoor unit PCB (main).
2 Faulty indoor unit PCB (main).
3 Indoor-outdoor signal transmission error due to wrong wiring.
4 Indoor-outdoor signal transmission error due to breaking of wire in the connection wires between the indoor
and outdoor units.
5 Indoor-outdoor signal transmission error due to disturbed power supply waveform.
Abnormality Judgment:
Continue for 1 minute after operation.

Содержание

Узнайте о возможных неисправностях передачи сигналов между внутренним и наружным блоками. Обратите внимание на причины и решения для нормальной работы системы.

Скачать