S+S Regeltechnik AERASGARD RFTM-PS-CO2 [19/32] 3 4 5 6 7 8 9

S+S Regeltechnik AERASGARD RFTM-PS-CO2 [19/32] 3 4 5 6 7 8 9
19
F
AERASGARD
®
RPS - SD RFTM - PS - xx
Rev. 2022 - V12
Schéma de raccordement
RFTM - PS - CO2 - W
Schéma de raccordement
RPS - SD
1 2 3
123
ON
DIP
PS
Sensor
PS
–UB GND
+UB 24V AC/DC
Output PM
[µg/m³]
Plug for
4
5
6
1 2 3
SET REL.
OFFSET
ZERO
CO2 CO2 r.H.°C
121113
123 456 789
ON
DIP
ON ON
PS CO2 Mode
Sensor
CO2
Sensor
PS
NC = Normally Closed
COM = Common
NO = Normally Open
Plug for
display
–UB GND
+UB 24V AC/DC
Output CO2
[ppm]
NC
COM
NO
relay
switch
point
humidity [% r.H.]
fine dust [
µg/m
3
]
Outputs
temperature
[
°C
]
Plug for
Interrupteur DIP
RFTM - PS
- xx
Particules fines
(
PM
)
Plage de mesure DIP 1 DIP 2
0...50 µg/m
3
OFF OFF
0...100 µg/m
3
(default)
O N
OFF
0...300 µg/m
3
OFF
O N
0...500 µg/m
3
O N O N
Particules fines
(
PM
)
Taille de particules DIP 3
PM 2,5 (default)
O N
PM 10 OFF
Teneur en CO2 DIP 4
0...2000 ppm (default) OFF
0...5000 ppm
O N
Étalonnage automatique CO2
DIP 6
désactivé OFF
activé (default)
O N
Affectation relais DIP 7 DIP 8
CO2 (default) 600...1900 ppm / 900...4700 ppm OFF OFF
Particules fines 10 %...95 % de la plage de mesure
O N
OFF
Température +5...+48 °C OFF
O N
Humidité 10...95% h.r.
O N O N
Sortie DIP 9
Tension 0 -10 V (default) OFF
Courant 4...20 mA
O N
Remarque:
DIP 5
n’est pas affecté !
Interrupteur DIP
RPS - SD
Particules fines
(
PM
)
Plage de mesure DIP 1 DIP 2
0...50 µg/m
3
OFF OFF
0...100 µg/m
3
(default)
O N
OFF
0...300 µg/m
3
OFF
O N
0...500 µg/m
3
O N O N
Particules fines
(
PM
)
Taille de particules DIP 3
PM 2,5 (default)
O N
PM 10 OFF

Содержание