Outlet Configuration
This page lets you set up the power management configuration for the selected
outlet. The meanings of the field headings are described in the following table
:
Heading Meaning
Outlet Name Each outlet can be given a distinctive name. The maximum number of
characters is 15.
Confirmation
Required
When enabled (checked), users are prompted to confirm every power
operation before it is performed. When disabled (unchecked), power
operations are performed without confirmation.
Power ON
Delay
Sets the amount of time the eco PDU shall wait for after the Power
Button is clicked (see Bank Status, page 33), before it powers on the
outlet.
Note: The default delay time is 0 seconds; the maximum is 999 seconds. When a
series of outlets are scheduled to be powered up, they turn on in sequence with a
default delay of 10 milliseconds between each outlet.
Power OFF
Delay
Sets the amount of time the eco PDU shall wait for after the Power
Button is clicked (see Bank Status, page 33), before it turns off the
outlet’s power.
For the System after AC Back option (see below), after the delay time
expires, the eco PDU waits for another fifteen seconds, then shuts
down the computer.
The default delay time is 15 sec; the maximum delay time is 999 sec.
Remote Turn
ON Method
Use the drop-down menu to select one of the following:
Wake on LAN: This is a safe shutdown and restart option. If selected,
when an Outlet is turned Off, the eco PDU first sends a message to
the computer telling it to prepare for a shutdown; it then waits for the
amount of time set by the Power Off Delay field to give the OS time to
shut down before the computer is powered down to standby mode.
Likewise, when the Outlet is turned On, the eco PDU waits for the
amount of time set by the Power On Delay field, then sends an
Ethernet message to the computer connected to the Outlet, telling the
computer to turn itself On.
Note: For
s
afe
s
hutdown and restart, the computer must be running Windows
(98 or higher), or Linux, with the safe shutdown program (available by download
from our website), installed and running.
System after AC Back: This is a safe shutdown and restart option. If
selected, when an Outlet is turned Off, the eco PDU first sends a
message to the computer telling it to prepare for shutdown; it then
waits for the amount of time set by the Power Off Delay field to give
the OS time to shut down before the computer is powered down.
When the Outlet is turned On, the eco PDU waits for the amount of
time set by the Power On Delay field, then sends power to the server.
When the server receives power, it shall turn itself on.
Note: For
s
afe
s
hutdown and restart, the computer must be running Windows
(98 or higher), or Linux, with the safe shutdown program (available by download
from our website), installed and running.