Installation
308778U 9
Grounding
1. Ground the flow meter by connecting a grounded
cable to the meter housing or sensor.
Have a qualified electrician check the electrical
grounding continuity between the flow meter sensor
and a true earth ground; remove the cable connec-
tor from the sensor and measure the resistance
from the cable connector Pin 2 to true earth ground.
Refer to F
IG. 3.
If the resistance is greater than 25 ohms, check the
cable ground connection. Refer to F
IG. 3. Recon-
nect the ground sheath or replace the cable. Do not
operate the system until the problem is corrected.
2. Always ground the meter, using one of the following
options:
a. Mount the meter to a grounded conductive sur-
face, or
b. Connect the conductive fluid hose to the meter
inlet and outlet, or
c. Connect a ground wire to the meter's M6
mounting holes.
3. Never use the flow meter with an electrostatic gun
isolation stand.
Meter Cables and Adaptor
See Table 1 for available meter cables or the adaptor for
use with cables with a black plastic connector and a
replacement sensor.
The equipment must be grounded to reduce the
risk of static sparking and electric shock. Electric or
static sparking can cause fumes to ignite or
explode. Improper grounding can cause electric
shock. Grounding provides an escape wire for the
electric current.
FIG. 3
TI26838a
1 +10-30 Vdc Supply (red)
2 Ground (black)
3 Signal Out (white)
1
3
2
Table 1: Meter Cables
Cable Part No. Length Ferrite Platform
17C743 5 ft (1.52 m) Various
17C910 42 in. (1029 mm) 15D906 ProMix 2KS
17C887 6 ft (1.83 m) Various
17C888 50 ft (15.25 m) Various
17C889 150 ft (45.75 m) Various
24Y434 Adaptor - Not included with cables (see note)
NOTE: These cables have a metal connector, which will only mate with a sensor that
also has a metal connector. Adaptor 24Y434 is required to connect an existing cable
with a plastic connector to a replacement sensor, which has a metal connector.
Adaptor 24Y434 purchased separately.
Содержание
- Instructions parts p.1
- Important safety instructions p.1
- For precise metering of plural component fluids or solvents depending on model for professional use only p.1
- Volumetric fluid flow meter p.1
- Contents p.2
- Solvent meter kit p.3
- Meter models p.3
- Meter kits p.3
- Low pressure fluid meters p.3
- High pressure solvent meter p.3
- High pressure fluid meters p.3
- G3000 fluid meter kits p.3
- Warnings p.4
- Installation p.7
- Installing the flow meter p.7
- Dust and foreign matter p.7
- Atex certificate its12atex27565x system assembly certificate p.8
- Intrinsically safe installation requirements p.8
- Intrinsically safe installation p.8
- Meter cables and adaptor p.9
- Grounding p.9
- Recommended usage p.10
- Pressure relief procedure p.10
- Operation p.10
- Flow volume range p.10
- Flow meter function p.10
- Checking the meter accuracy p.10
- Troubleshooting p.11
- Maintenance p.12
- Flushing p.12
- Residue build up on the meter gears p.12
- Replacing the electronic sensor p.13
- Cleaning or servicing the meter chamber p.13
- Cleaning or servicing the solvent meter p.14
- V827 g3000hr meter kit p.15
- V804 g3000 meter kit p.15
- S3000 solvent meter kit p.15
- Flow meter kits for promix 2ks wall fluid panel p.15
- G3000 meter p.16
- G3000hr meter p.16
- Bare meter assemblies p.16
- G250hr meter p.17
- G250 meter p.17
- Solvent meter assembly p.18
- S3000 meter p.18
- Part nos 289813 and 289814 p.20
- Part nos 249426 and 249427 p.20
- Mounting holes bottom p.20
- G3000 and g3000hr p.20
- G250 and g250hr p.20
- Dimensions p.20
- Solvent meter p.21
- Part no 258718 p.21
- Part no 15u749 p.21
- Mounting holes bottom p.21
- Kit mounting bracket p.21
- Volumetric fluid flow meters p.22
- Technical data p.22
- Pressure drop curve p.23
- To place an order contact your graco distributor or call to identify the nearest distributor phone 612 623 6921 or toll free 1 800 328 0211 fax 612 378 3505 p.24
- Graco headquarters minneapolis international offices belgium china japan korea p.24
- For the latest information about graco products visit www graco com p.24
- Graco standard warranty p.24
- Graco information p.24
- Graco inc and subsidiaries p o box 1441 minneapolis mn 55440 1441 usa copyright 1997 graco inc all graco manufacturing locations are registered to iso 9001 www graco com revised november 2015 p.24
Похожие устройства
-
Graco EM8, жесткий носик, 1/2" NPT 25C903Инструкция к Graco EM8 25C903 -
Graco CoriolisСхема сборки -
Graco CoriolisИнструкция по эксплуатации -
Graco HG6000HRТехнические характеристики -
Graco HG6000HRИнструкция по эксплуатации -
Graco HG6000Технический паспорт -
Graco HG6000Инструкция по эксплуатации -
Graco S3000Технические характеристики -
Graco G3000HRТехнические характеристики -
Graco G3000HRИнструкция по эксплуатации -
Graco G3000Технические характеристики -
Graco G3000Инструкция по эксплуатации
Узнайте, как правильно заземлить расходомер для предотвращения электрических ударов и искрения. Следуйте инструкциям для безопасной эксплуатации оборудования.