Moxa ICF-1180I-S-ST-T [10/16] Dip switch settings
![Moxa ICF-1180I-S-ST-T [10/16] Dip switch settings](/views2/1201043/page10/bga.png)
- 10 -
L: The length of the fiber optic cable in kilometers.
N: The number of converters in the system.
A and B: Parameters determined by the transmission speed.
Note: To avoid frame conflicts, we recommend setting the PROFIBUS
command retry limit ≥ 3, and the slot time < 262128.
DIP Switch Settings
There are 8 DIP switches on the top panel of the ICF-1180I. The factory
default setting for all DIP switches, except SW5, is OFF.
Transmission Speed (kbps)
SW1
SW2
SW3
SW4
Auto (default)
OFF
OFF
OFF
OFF
12000
OFF
OFF
OFF
ON
6000
OFF
OFF
ON
OFF
3000
OFF
OFF
ON
ON
1500
OFF
ON
OFF
OFF
500
OFF
ON
OFF
ON
187.5
OFF
ON
ON
OFF
93.75
OFF
ON
ON
ON
45.45
ON
OFF
OFF
OFF
19.2
ON
OFF
OFF
ON
9.6
ON
OFF
ON
OFF
Setting
ON
OFF
SW5
Fiber Link Monitor
Disable
SW6
Reserved
Reserved
SW7
Reserved
Reserved
SW8
Remote Fiber Diagnosis*
Disable
* Refer to the Remote Fiber Diagnosis section for instructions.
ATTENTION
If you connect an ICF
-
1180I converter running firmware version
1.2 to (a) an ICF
-
1180I converter running firmware version 1.3
or above, or (b) an ICF
-1280I converter, the built-in
Fiber Link
Monitor
and Fiber Test
functions may not work properly. Users
mus
t disable the Fiber Link Monitor function through the DIP
switch and the
Fiber Test function will work in this situation.
Version 1.3 of the ICF
-1180I converter is fully compatible with
the ICF
-1280I series for the Fiber Link Monitor
function and the
Remot
e Fiber Diagnosis function.
Version 1.4 of ICF
-1180I converter change the function name
"Fiber Test" to "Remote Fiber Diagnosis"
Содержание
- Edition 7 may 2016 1
- Icf 1180i series quick installation guide 1
- Auto manual baudrate settings 2
- Introduction 2
- Why convert profibus to fiber 2
- Fiber link monitor 3
- Profibus fail safe 3
- Remote fiber diagnosis 3
- Reverse power protection 3
- Features 4
- Package checklist 4
- Mounting dimensions unit mm 5
- Attention 6
- Bottom view 6
- Front view 6
- Icf 1180i panel layouts 6
- Top view 6
- Mounting 7
- Wiring the alarm contact 7
- Attention 8
- Fiber cable 8
- Pin assignment 8
- Wiring the redundant power inputs 8
- Atex and iecex information 9
- Federal communications commission statement 9
- Slot time settings 9
- Attention 10
- Dip switch settings 10
- Led indicators 11
- Attention 12
- Troubleshooting led indicators and fiber test 12
- Fiber signal intensity diagnosis 13
- Specifications 15
Похожие устройства
- Moxa ICF-1180I-S-ST-T Технические характеристики
- Moxa ICF-1280I-M-ST Инструкция по эксплуатации
- Moxa ICF-1280I-M-ST Технические характеристики
- Moxa ICF-1280I-M-ST-T Инструкция по эксплуатации
- Moxa ICF-1280I-M-ST-T Технические характеристики
- Moxa ICF-1280I-S-ST Инструкция по эксплуатации
- Moxa ICF-1280I-S-ST Технические характеристики
- Moxa ICF-1280I-S-ST-T Инструкция по эксплуатации
- Moxa ICF-1280I-S-ST-T Технические характеристики
- Moxa ioLogik E1210 Инструкция по эксплуатации
- Moxa ioLogik E1210 Руководство по аппаратной части
- Moxa ioLogik E1210 Технические характеристики
- Moxa ioLogik E1210 Брошюра
- Moxa ioLogik E1210-T Инструкция по эксплуатации
- Moxa ioLogik E1210-T Руководство по аппаратной части
- Moxa ioLogik E1210-T Технические характеристики
- Moxa ioLogik E1210-T Брошюра
- Moxa ioLogik E1211 Инструкция по эксплуатации
- Moxa ioLogik E1211 Руководство по аппаратной части
- Moxa ioLogik E1211 Брошюра