Moxa ICF-1180I-S-ST-T [4/16] Features

Moxa ICF-1180I-S-ST-T [4/16] Features
- 4 -
Using Remote Fiber Diagnosis:
Set DIP switch SW8 to the ON position on any ICF-1180I converter and
then look at the Ready LED status. A flashing green Ready LED indicates
that the Fiber Test has finished. The P1 (Fiber port) LED indicates which
side (Tx or Rx) is causing the problem. If there are no fiber connection
errors in the entire topology, the related LEDs will shine green or remain
OFF. If the fiber connection error is adjacent to the converter, the status
will also be indicated by the P1 LEDs. A flashing red light on P1 means that
the Rx fiber cable connected to this port is broken. Similarly, a solid red
light on P1 means that the Tx fiber cable in this port is broken. Further
descriptions and troubleshooting can be found in the Troubleshooting
table.
Features
Auto baudrate detection and data speed up to 12 Mbps
PROFIBUS bus fail safe
Alarm by relay output
2 kV galvanic isolation
Power polarity protection
Extends PROFIBUS transmission distance:
Up to 45 km with single-modeICF-1180I-S series
Up to 4 km with multi-modeICF-1180I-M series
Remote Fiber Diagnosis
Topology: Point-to-Point mode, Linear mode (as the head or tail
converter with ICF-1280I)
Dual power inputs for redundancy
Wide operating temperature range: -40 to 75°C (for “T” models)
Supports Fiber Signal Intensity Diagnosis
Package Checklist
Before installing the ICF-1180I converter, verify that the package
contains the following items:
ICF-1180I PROFIBUS-to-fiber converter
Quick installation guide (printed)
Warranty card
Note: Please notify your sales representative if any of the above items are
missing or damaged.