Moxa ICF-1180I-S-ST-T [11/16] Led indicators

Moxa ICF-1180I-M-ST-T [11/16] Led indicators
- 11 -
LED Indicators
There are 6 LEDs on the front panel of the ICF-1180I.
LED
Color
Description
Relay Status
PWR1/
PWR2
Solid green
Power is on
Closed
Off
Power is off, or power error
condition exists
Open
Ready
Solid green
Baudrate is detected,
converter is ready for
communication
Closed
Flashing
green*
Fiber diagnosis is finished
Closed
Flashing red*
Detecting baudrate
Closed
Flashing red
and green*
Slotting time setting error
Closed
Off
System power is off
Closed
P1 Level
Green
Fiber Component Strength
Normal
Closed
Orange
Fiber Component Strength
is in the critical level, it
might abnormal soon.
Closed
Red
Fiber Component strength is
fail or Fiber cable too long
Open
P1
(Fiber)
Flashing/
solid green
Fiber port is receiving data
Closed
Solid red*
Fiber cable linking to Tx is
abnormal
Open
Flashing red*
Fiber cable linking to Rx is
abnormal
Open
Off
Fiber in idle state
Closed
P2
(PROFIBUS)
Flashing
green
PROFIBUS port is
communicating
Closed
Flashing red
Inner transceiver IC
defective;
PROFIBUS port data
communication error;
insufficient shielding of the
bus cable; echo package
timeout
Open
Solid red
Echo package timeout,
PROFIBUS UART character
error
Open
Off
PROFIBUS in idle state
Closed
If both power inputs experience an outage, the relay will become an open
circuit for alarm purposes.
* Refer to the following table for troubleshooting information.