Moxa ICF-1180I-S-ST-T [7/16] Mounting

Moxa ICF-1180I-M-ST [7/16] Mounting
- 7 -
Mounting
The aluminum DIN rail attachment plate should be fixed to the back panel
of the ICF-1180I when you take it out of the box. If you need to reattach
the DIN rail attachment plate to the ICF-1180I, make sure the stiff metal
spring is situated towards the top, as shown in the figures below.
STEP 1:
Insert the top
of the DIN rail into
the slot just below the stiff metal
spring.
STEP 2:
The DIN
-rail attachment unit will
snap into place as shown below.
To remove the ICF-1180I series from the DIN rail, simply reverse Steps 1
and 2 above.
Wiring the Alarm Contact
The alarm contact is made up of the two middle contacts of the terminal
block on the ICF-1180I’s top panel. Refer to the next section for detailed
instructions on how to connect the wires to the terminal block connector,
and how to attach the terminal block connector to the terminal block
receptor.
In this section, we explain the meaning of the two contacts used to
connect the alarm contact.
FAULT: The two middle contacts of the 6-contact
terminal block connector are used to detect both
power faul
ts and port faults. The two wires
attached to the Fault contacts form an open
circuit when:
1. The ICF-1180I
has lost power from one of
the DC power inputs.
OR
2. One of the ports for which the
corresponding PORT ALARM Dip Switch is
set to ON is not properly connected.
If neither of these two conditions occurs, the
Fault circuit will be closed.