Moxa NA-4010 [41/94] Click go logic tab administrator

Moxa NA-4010 [41/94] Click go logic tab administrator
ioLogik E4200 Utilities
3-20
ATTENTION
When t
he ioLogik E4200 is in safe mode, you cannot start Click&Go logic and cannot change the module
configuration. The Host Connection Watchdog is disabled by default. If the Host Connection Watchdog is
disabled, the ioLogik I/O system will never enter Safe Status and the Safe Status settings will have no effect.
During
Host Connection Lost, the “I/O” LED will show a steady red to indicate that it is in Safe Mode. After
clear
ing the alarm, you must restart the system. If you see the I/O LED indicator flashing Red, power off
the
system
and power it on again to return to normal operation.
Click&Go Logic Tab (Administrator)
The Click&Go logic tab is used by the administrator to set up the ioLogik E4200’s Active I/O messaging logic.
Instead of the I/O device reacting passively to repeated polling requests from a host for I/O data, the ioLogik
E4200 can actively send I/O information to the host when an I/O channel satisfies conditions that you specify.
Click&Go logic was developed by Moxa to provide a powerful and easy-to-use tool for defining the conditions
under which I/O information will be sent over the network. Refer to Chapter 5 for detailed information.
Changes made on the Click&Go logic tab are not effective until you download the logic and the ioLogik E4200
is restarted, as with changes made to other tabs.
ATTENTION
Note that when Click&Go
logic is being used, the range and units of I/O channels being used in Click&Go l
ogic
cannot be modified.