Moxa ioLogik E2214 [19/90] Digital input mode selection

Moxa ioLogik E2262 [19/90] Digital input mode selection
Click&Go V2 Click&Go V2 Developing Process
3-3
Digital Input Mode Selection
A DI channel can be set to “DI” or “Event Counter” mode. In DI mode, it connects to dry/wet contacts.
In Event Counter mode, the channel accepts limit or proximity switches and counts events according to the
ON/OFF status. When Lo to Hiis selected, the counter value increases when the attached switch is pushed.
When Hi to Lois selected, the counter value increases when the switch is pushed and released.
Mode Available
Number of Digital
Input Channels
Mode Selection:
DI
Mode Selection:
Event Counter
ioLogik E2210 12
ioLogik E2212 8 + 4 DIO
ioLogik E2214 6
ioLogik E2242 12 DIO
When logged in as an administrator, double click on a channel in the I/O Configuration tab to configure that
channels settings. A window will open with configuration options for that channel. Each DI channel will be
configured to act as either a DI or Event Counter channel, according to the Mode Settings. To switch between
DI and Event Counter channel operation, select the desired mode in the Mode Settings.
ATTENTION
On this tab, be sure to select
Startfor the Counter Mode Parameters on the Power On Settings
to enable
the Event Counter channel.