Castel MAC TC 60 N [12/17] Managing and silencing detected alarms

Castel MAC TC 60 N [12/17] Managing and silencing detected alarms
12
GB
6.1 Storing alarms
The controller is equipped with visual and
acoustic signalling of alarms caused by
appliance operation anomalies.
A maximum of 16 alarm events are stored;
further alarms will overwrite those already
recorded. The alarms are signalled by a
buzzer and the display will show the type of
alarm.
There is signalling delay only for HIGH/LOW
cell temperature alarms, which are signalled
60 minutes after being detected.
The controller will show the HIGH or LOW
temperature pre-alarm on the display, storing
it in the alarms list when the time has
elapsed.
Cell high temperature pre-alarm message
Cell low temperature pre-alarm message
When the pre-alarm time has elapsed the
controller will show the following message:
To cancel the alarm enter the
MENU 1
ALARMS LIST.
6.2 Silencing alarms
To silence the buzzer during an alarm press
the
ENTER button
6.3 Alarms list
It is possible to display the alarms that the
controller stored during its operation.
To enter the display press
MENU, with the
or buttons go to
MENU 1 ALARMS
LIST and press ENTER.
Using the or buttons scroll the alarms
stored by the controller.
The controller stores the type of alarm, the
start date of the alarm and its duration in
minutes.
If the and buttons are pressed at the
same time the date of the last alarm reset is
displayed. The maximum and minimum tem-
perature alarm also displays the maximum
and minimum temperatures reached.
In the blackout alarm the date/time of power
failure start and finish is recorded. If no
alarms have been stored the controller dis-
plays
NO EVENTS IN MEMORY.
Example of high temperature alarm:
AL 27: HIGH TEMP.
Duration 015’
AL 27: HIGH TEMP.
S.=18/03/02 12:29
AL 27: HIGH TEMP.
Max Temp.= +25°C
ALARM DETECTED
CELL -24,0 °C
PAUSE >>Lt
CELL -24°C
COOLING >>Ht
Cell -18°C
6. MANAGING AND SILENCING
DETECTED ALARMS