11
GBGB
5.1 Manual defrost
A manual defrost can be activated: press the
MENU button, with the or buttons go
to MENU 4 DEFROST and press the ENTER
button.
The controller requests a further confirma-
tion, displaying
EXIT or CONFIRM. Press the
button to confirm or the
ENTER button to
exit and return to the first box.
Message with defrost active:
At the end of defrosting the compressor will
restart and the display will show the word
REGENERATION until the set-point tempera-
ture is reached.
Defrosting is completed when the set-point is
reached (detected by the two sensors locat-
ed on the evaporator) or when the maximum
defrost time is reached.
In the case of maximum time being reached
the controller signals the anomaly with the
following intermittent alarm message and the
buzzer:
The controller memorises the type of alarm,
date and time.
To cancel the alarm message press the
ENTER button.
In any case, the alarm is stored in the con-
troller’s alarms memory.
5.2 Periodic defrosting
For all models, defrosting can be repeated
automatically at regular intervals, beginning
immediately after the appliance is switched
on.
The time between automatic defrosts is fac-
tory-set at 6 hours.
Also in this case, defrosting is completed on
reaching the set-point (detected by the two
sensors on the evaporator) or when the max-
imum defrost time is reached.
The anomaly is signalled as in the case of
manual defrosting.
5.3 Timed defrosting
It is possible to set the starting time for 4 daily
automatic defrosts that will always be repeat-
ed in a 24-hour time period. In this mode,
automatic periodic defrosts are disabled.
Defrosting is completed as described above.
F18 DEFROST TIME
S 19/02/02 06:09
DEFROST TIME
—> Call SERVICE
REGENERATION >>OK
CELL -10,5°C
DEFROST >>OK
CELL -18°C
Menu 4
DEFROST
5. DEFROST MANAGEMENT