Chigo CS/CU-25H3A-V84 [5/13] 三 portable air conditioner serial
![Chigo CS/CU-25H3A-V84 [5/13] 三 portable air conditioner serial](/views2/1324982/page5/bg5.png)
5
the unit is running.
3、 Check whether the indoor and outdoor wiring is right;
when it is wrong, connect them again according to the
circuit diagram
4、Check whether the contact of the inserter on the circuit
board and the connection are well, otherwise repair.
5、Check whether the signal feedback wire is disconnected,
replace or connect the feedback signal wire.
6、Check whether the supply power is phase-lacking or
phase opposition.
7、Check whether the AC electromagnetic contactor is well.
E8
display at
off state
flicker 8/10
SEC
display
at off
state
frost
protection
/over heat
protection
1、 Check whether the filter of the indoor unit is dirty or
blocked, and clean if it is dirty.
2、Check whether the indoor fan is running normally, and
replace the motor if it is abnormal.
3、Check whether indoor pipe temperature sensor is normal,
and replace the sensor if it is abnormal.
4 、 Check whether the system pressure is normal, if
abnormal, should check whether there is leakage, and fill
the refrigerant again.
三、portable air conditioner serial
LED lamp display
code explain code explain
failure
The reason of fault and solution
E2
display at
off state
room temp.
sensor fault
1、Check whether the resistance of the sensor is
normal (the resistance is 5КΩ in the normal
temperature 25 )℃ , when it is abnormal the sensor
should be replaced.
2、Check whether there is short circuit or open circuit
in the wire of the sensor, and whether the plug is
connected well, whether there is welding off or
rosin joint on the electric control board, if there is
any, it should be repaired.
3、When the 1 and 2 are both normal, then the
components or integrated circuit is damaged, the
electric control board should be replaced.
E3
display at
off state
coil
temp. sensor
fault
1、 Check whether the resistance of the sensor is
normal (the resistance is 5КΩ in the normal
temperature 25 )℃ , when it is abnormal the sensor
should be replaced.
2、Check whether there is short circuit or open circuit
in the wire of the sensor, and whether the plug is
connected well, whether there is welding off or
rosin joint on the electric control board, if there is
any, it should be repaired.
3、When the 1 and 2 are both normal, then the
Содержание
Похожие устройства
- Chigo CS/CU-25H3A-V84 Каталог Chigo 2011
- Chigo CS/CU-61H3A-P84 Инструкция по эксплуатации
- Chigo CS/CU-61H3A-P84 Сертификат
- Chigo CS/CU-61H3A-P84 Коды ошибок
- Chigo CS/CU-61H3A-P84 Каталог Chigo 2011
- Chigo CS/CU-21H3A-V84 Инструкция по эксплуатации
- Chigo CS/CU-21H3A-V84 Сертификат
- Chigo CS/CU-21H3A-V84 Коды ошибок
- Chigo CS/CU-21H3A-V84 Каталог Chigo 2011
- Rix I/O-W12S Инструкция по эксплуатации
- Rix I/O-W12S Инструкция по монтажу
- Rix I/O-W18S Инструкция по эксплуатации
- Chigo CS/CU-51H3A-P84 Инструкция по эксплуатации
- Chigo CS/CU-51H3A-P84 Сертификат
- Chigo CS/CU-51H3A-P84 Коды ошибок
- Chigo CS/CU-51H3A-P84 Каталог Chigo 2011
- Rix I/O-W09S Инструкция по эксплуатации
- Rix I/O-W09S Инструкция по монтажу
- Chigo CS/CU-32H3A-V84 Инструкция по эксплуатации
- Chigo CS/CU-32H3A-V84 Сертификат
Скачать
Случайные обсуждения