Chigo CS/CU-25H3A-V84 [2/13] 一 wall split ac series
![Chigo CS/CU-25H3A-V84 [2/13] 一 wall split ac series](/views2/1324982/page2/bg2.png)
2
一、wall split AC series
LED lamp display
code explain code explain
failure
The reason of fault and solution
DF
display at
on state
flicker 1/1
SEC
defrost
indication
Normal, the defrost state is removed, it will return to
normal condition automatically
display at
off state
flicker 1/3
SEC
anti cold wind
1、 Normal (during heating mode )
2、It will be removed when the coil pipe temperature
sensor reaches certain temperature.
E2
display at
off state
flicker 1/1
SEC
display
at on/off
state
room temp.
sensor fault
1、Check whether the resistance of the sensor is normal
(the resistance is 5КΩ in the normal temperature
25 )℃ , when it is abnormal the sensor should be
replaced.
2、Check whether there is short circuit or open circuit in
the wire of the sensor, and whether the plug is
connected well, whether there is welding off or
rosin joint on the electric control board, if there is
any, it should be repaired.
3、When the 1 and 2 are both normal, then the
components or integrated circuit is damaged, the
electric control board should be replaced.
E3
display at
off state
flicker 3/5
SEC
display
at on/off
state
coil temp.
sensor fault
1、Check whether the resistance of the sensor is normal
(the resistance is 5КΩ in the normal temperature
25 )℃ , when it is abnormal the sensor should be
replaced.
2、Check whether there is short circuit or open circuit in
the wire of the sensor, and whether the plug is
connected well, whether there is welding off or
rosin joint on the electric control board, if there is
any, it should be repaired.
3 、When the 1 and 2 are both normal, then the
components or integrated circuit is damaged, the
electric control board should be replaced.
E4
display at
on/off
state
flicker 4/6
SEC
display
at off
state
outdoor unit
abnormal
1、 Check whether the winding resistance and
operation current of the compressor are normal.
2、Check whether the high and low pressure is normal
when the unit is running.
3、Check (whether the coil pipe sensor is normal)
whether the contact of the inserter on the circuit
board is well, the coil pipe temperature sensor is
fixed, the evaporation of the indoor unit is well,
the key is to check the evaporator temperature
detected by the coil pipe temperature sensor has
reached the cooling or heating temperature.
4、Check whether the surface of the condenser is too
dirty, it should be cleaned when it is too dirty.
5、Check whether the capacitance of the outdoor motor
and the fan is damaged, it should be replaced when
Содержание
Похожие устройства
- Chigo CS/CU-25H3A-V84 Каталог Chigo 2011
- Chigo CS/CU-61H3A-P84 Инструкция по эксплуатации
- Chigo CS/CU-61H3A-P84 Сертификат
- Chigo CS/CU-61H3A-P84 Коды ошибок
- Chigo CS/CU-61H3A-P84 Каталог Chigo 2011
- Chigo CS/CU-21H3A-V84 Инструкция по эксплуатации
- Chigo CS/CU-21H3A-V84 Сертификат
- Chigo CS/CU-21H3A-V84 Коды ошибок
- Chigo CS/CU-21H3A-V84 Каталог Chigo 2011
- Rix I/O-W12S Инструкция по эксплуатации
- Rix I/O-W12S Инструкция по монтажу
- Rix I/O-W18S Инструкция по эксплуатации
- Chigo CS/CU-51H3A-P84 Инструкция по эксплуатации
- Chigo CS/CU-51H3A-P84 Сертификат
- Chigo CS/CU-51H3A-P84 Коды ошибок
- Chigo CS/CU-51H3A-P84 Каталог Chigo 2011
- Rix I/O-W09S Инструкция по эксплуатации
- Rix I/O-W09S Инструкция по монтажу
- Chigo CS/CU-32H3A-V84 Инструкция по эксплуатации
- Chigo CS/CU-32H3A-V84 Сертификат
Скачать
Случайные обсуждения