二、floor standing AC serial
LED lamp display
code explain code explain
failure
The reason of fault and solution
E2
display at
off state
flicker 2/4
SEC
display
at on/off
state
room temp.
sensor
fault
1Check whether the resistance of the sensor is normal (the
resistance is 5КΩ in the normal temperature 25 ) ,
when it is abnormal the sensor should be replaced.
2Check whether there is short circuit or open circuit in the
wire of the sensor, and whether the plug is connected
well, whether there is welding off or rosin joint on the
electric control board, if there is any, it should be
repaired.
3When the 1 and 2 are both normal, then the components
or integrated circuit is damaged, the electric control
board should be replaced.
E3
display at
off state
flicker 3/5
SEC
display
at on/off
state
coil temp.
sensor
fault
1 Check whether the resistance of the sensor is normal
(the resistance is 5КΩ in the normal temperature 25 ) ,
when it is abnormal the sensor should be replaced.
2Check whether there is short circuit or open circuit in the
wire of the sensor, and whether the plug is connected
well, whether there is welding off or rosin joint on the
electric control board, if there is any, it should be
repaired.
3When the 1 and 2 are both normal, then the components
or integrated circuit is damaged, the electric control
board should be replaced.
E4
display at
on/off
state
flicker 4/6
SEC
display
at off
state
outdoor
unit
abnormal
1 Check whether the winding resistance and operation
current of the compressor are normal.
2Check whether the high and low pressure is normal when
the unit is running.
3Check (whether the coil pipe sensor is normal) whether
the contact of the inserter on the circuit board is well, the
coil pipe temperature sensor is fixed, the evaporation
of the indoor unit is well, the key is to check the
evaporator temperature detected by the coil pipe
temperature sensor has reached the cooling or heating
temperature.
4 Check whether the surface of the condenser is too dirty,
it should be cleaned when it is too dirty.
5Check whether the capacitance of the outdoor motor and
the fan is damaged, it should be replaced when it is
damaged.
6If the above items are normal, the electric control board
should be replaced.
E7
display at
off state
flicker 7/9
SEC
display
at off
state
outdoor
feedback
fault
1Check whether the winding resistance and operation
current of the compressor are normal
2Check whether the high and low pressure is normal when