Chigo CS/CU-25H3A-V84 [10/13] 六 dc inverter multi split series

Chigo CS/CU-51H3A-P84 [10/13] 六 dc inverter multi split series
10
protection
2Check whether the sensor, connecting wire of the sensor
and the detection circuit are abnormal.
P5 5 light
over heat of
compressor top
protection
1Check whether the air condition system and pressure are
normal.
2Check whether the sensor, connecting wire of the sensor
and the detection circuit are abnormal.
P6 6 light
suction temp. of
compressor
protection
1Check whether the air condition system and pressure are
normal.
2Check whether the sensor, connecting wire of the sensor
and the detection circuit are abnormal.
P7 7 light
low or high voltage
protection
1Check whether the supply voltage is out of rang from
150 to 270V
2Check the voltage detection circuit of the IPM base
board is abnormal, if it is abnormal, the IPM base board
or the electric control board should be replaced.
P8 8 light
low presser of gas
return protection
1 Check whether the pressure is normal when the unit is
running, if it is abnormal, should detect the leakage and
welding add refrigerant.
P9 9 light
high pressure of
discharge
protection
1Check whether the pressure is normal when the unit is
running, if it is abnormal, should detect the leakage and
welding add refrigerant.
PA 10 light
high temp. of
condenser
protection
1、Check whether the condenser of outdoor unit is too dirty,
and it should be cleaned when it is too dirty.
2、Check whether it is running at bad condition long
time.
3、Check whether senor and wire are normal.
PC 11 light
high temp. of
outdoor ambient
protection
1Check the outdoor ambient temperature is too high or
there is heat source around the outdoor unit.
2Check whether the sensor and sensor wire are normal.
PF 12 light other protection
六、DC inverter multi-split series
LED failure
The reason of fault and solution
F1 communicate fault
1Check whether the connection of the outdoor unit and indoor unit is
one to one.
2Check whether the unit is abnormal caused by the external
interference, if it is, then find the interfering source, and removes it.
3、Check whether the electrical control board is damage, it
should be replaced when it is damaged.
F2 indoor temp. sensor fault
1 Check whether the resistance of sensor is normal, otherwise replace
it.
2Check whether the sensor wire is short circuit or open circuit, and
whether the plug is well contacted, whether there is welding off or
rosin joint on the electric control board, repair it if there is any
above.