3、 When the 1 and 2 are both normal, then the components or
integrated circuit is damaged, the electric control board should be
replaced.
F3
outlet e temp. sensor of indoor unit
coil pipe fault
1、Check whether the resistance of sensor is normal, otherwise replace
it.
2、Check whether the sensor wire is short circuit or open circuit, and
whether the plug is well contacted, whether there is welding off or
rosin joint on the electric control board, repair it if there is any
above.
3、When the 1 and 2 are both normal, then the components or
integrated circuit is damaged, the electric control board should be
replaced.
F3
suction temp. sensor of indoor
unit coil pipe fault
1、Check whether the resistance of sensor is normal, otherwise replace
it.
2、Check whether the sensor wire is short circuit or open circuit, and
whether the plug is well contacted, whether there is welding off or
rosin joint on the electric control board, repair it if there is any
above.
3、When the 1 and 2 are both normal, then the components or
integrated circuit is damaged, the electric control board should be
replaced.
F3
middle temp. sensor of indoor unit
coil pipe fault
1、Check whether the resistance of sensor is normal, otherwise replace
it.
2、Check whether the sensor wire is short circuit or open circuit, and
whether the plug is well contacted, whether there is welding off or
rosin joint on the electric control board, repair it if there is any
above.
3、 When the 1 and 2 are both normal, then the components or
integrated circuit is damaged, the electric control board should be
replaced.
F4 PG motor fault
1、Check whether the contact of the plug of the motor wire and socket
is well, making sure well contact.
2、Check whether the indoor motor has damaged, the motor should be
replaced when it is damaged.
3、Check whether the controllable silicon and other components on the
electric control board have damaged, replace the controllable
silicon or electric control board when they are damaged.
P2 protection of module fault
1、Check whether the connection of the compressor is reliable,
otherwise connect firmly again.
2、Check whether the fixation between the IPM module and the
radiator is firm.
3、Check whether the compressor is well, otherwise replace it.
4、Check whether the IPM module is abnormal, otherwise replace it.
P3 over current of outdoor unit
1、Check whether the ambient temperature exceeds the operation range
for the air conditioner
2、Check whether the current detection circuit is abnormal, the electric
Содержание
Похожие устройства
- Chigo CS/CU-25H3A-V84 Каталог Chigo 2011
- Chigo CS/CU-61H3A-P84 Инструкция по эксплуатации
- Chigo CS/CU-61H3A-P84 Сертификат
- Chigo CS/CU-61H3A-P84 Коды ошибок
- Chigo CS/CU-61H3A-P84 Каталог Chigo 2011
- Chigo CS/CU-21H3A-V84 Инструкция по эксплуатации
- Chigo CS/CU-21H3A-V84 Сертификат
- Chigo CS/CU-21H3A-V84 Коды ошибок
- Chigo CS/CU-21H3A-V84 Каталог Chigo 2011
- Rix I/O-W12S Инструкция по эксплуатации
- Rix I/O-W12S Инструкция по монтажу
- Rix I/O-W18S Инструкция по эксплуатации
- Chigo CS/CU-51H3A-P84 Инструкция по эксплуатации
- Chigo CS/CU-51H3A-P84 Сертификат
- Chigo CS/CU-51H3A-P84 Коды ошибок
- Chigo CS/CU-51H3A-P84 Каталог Chigo 2011
- Rix I/O-W09S Инструкция по эксплуатации
- Rix I/O-W09S Инструкция по монтажу
- Chigo CS/CU-32H3A-V84 Инструкция по эксплуатации
- Chigo CS/CU-32H3A-V84 Сертификат
Скачать
Случайные обсуждения