12
control should be replaced when it is abnormal.
P4
discharge temp. of compressor too
high, outside ambient temp. too
high, temp. switch of compressor
crust cut off, temp. of module too
high.
1、Check whether the pressure is normal when the unit is running, if it
is abnormal, should detect the leakage and welding add
refrigerant.
2、Check whether ambient temp. is too high or too low, when
the temp. more than -20 degree and less 55 degree, it can
disappear automatically.
3、communicate interference, earth wire and communicate wire can’t
put in one cable.
4、Check whether temp. switch of compressor is damage, it
should be replace if it damaged.
P7 DC voltage abnormal of outdoor unit
1Check whether the supply voltage is out of rang from 150 to 270V
2Check the voltage detection circuit of the IPM base board is
abnormal, if it is abnormal, the IPM base board or the electric
control board should be replaced.
P8
lack refrigerant or reverse valve
fault
1Check whether the high and low pressure valves have been opened,
otherwise open the valves.
2Check whether the indoor coil pipe temperature sensor is normal, if
it is abnormal, the sensor should be replaced.
3Check the system pressure is abnormal, if it is abnormal, should
detect leakage repairing welding and adding the refrigerant.`
F6 outside sensor fault
1Check whether the resistance of sensor is normal, otherwise replace
it.
2Check whether the sensor wire is short circuit or open circuit, and
whether the plug is well contacted, whether there is welding off or
rosin joint on the electric control board, repair it if there is any
above.
3When the 1 and 2 are both normal, then the components or
integrated circuit is damaged, the electric control board should be
replaced.
FC
outdoor unit drive fault, start
compressor failure
1Power on again, and check the operation of the compressor is
normal.
2Check whether the connection of the compressor is reliable,
otherwise repair.
3Check whether the components on the electric control board have
been damaged, if they are damaged, the components or the electric
control board should be replaced.