board, repair it if there is any above.
3When the 1 and 2 are both normal, then the components
or integrated circuit is damaged, the electric control
board should be replaced.
FA 10 light
inductor of current
or voltage fault
1、Check whether inductor of current or voltage have been
damaged, they should be replaced if they are fault.
FC 11 light
compressor drive
fault
1Power on again, and check the operation of the
compressor is normal.
2Check whether the connection of the compressor is
reliable, otherwise repair.
3Check whether the components on the electric control
board have been damaged, if they are damaged, the
components or the electric control board should be
replaced.
FD 12 light
phase lacking or
phase sequence
fault
1、Check power wire voltage or change two power wires.
FE 13 light
gas return sensor
fault(include
A,B,C,D)
1Check whether the resistance of sensor is normal,
otherwise replace it.
2Check whether the sensor wire is short circuit or open
circuit, and whether the plug is well contacted, whether
there is welding off or rosin joint on the electric control
board, repair it if there is any above.
3When the 1 and 2 are both normal, then the components
or integrated circuit is damaged, the electric control
board should be replaced.
FF 14 light other fault
P1 1 light
temp. of evaporator
protection
1、Check whether the filter of indoor unit is too dirty, and it
should be cleaned when it is too dirty.
2、Check whether it has barrier around indoor unit,
it should be remove if it has.
3、Check whether the indoor motor is damaged, it should be
replaced motor or electrical control board when it is
damaged.
P2 2 light
overheat, over
current protection
of inverter module
1 Check whether the fixation between the IPM module
and the radiator is firm.
2Check whether the compressor is well, otherwise replace
it.
3Check whether the IPM module is abnormal, otherwise
replace it.
P3 3 light
over current
protection
1Check whether the ambient temperature exceeds the
operation range for the air conditioner
2Check whether the current detection circuit is abnormal,
the electric control should be replaced when it is
abnormal.
P4 4 light
discharge temp. of
compressor
1Check whether the air condition system and pressure are
normal.