unit fault
and socket is well, making sure well contact.
2、Check whether the indoor motor has damaged, the motor
should be replaced when it is damaged.
3、Check whether the controllable silicon and other
components on the electric control board have
damaged, replace the controllable silicon or electric
control board when they are damaged.
F5 5 light
module of outdoor
unit fault
1、Check whether the connection of the compressor is
reliable, otherwise connect firmly again.
2、Check whether the fixation between the IPM module and
the radiator is firm.
3、Check whether the compressor is well, otherwise replace
it.
4、 Check whether the IPM module is abnormal, otherwise
replace it.
F6 6 light
ambient temp.
sensor of outdoor
fault
1、Check whether the resistance of sensor is normal,
otherwise replace it.
2、Check whether the sensor wire is short circuit or open
circuit, and whether the plug is well contacted, whether
there is welding off or rosin joint on the electric control
board, repair it if there is any above.
3、When the 1 and 2 are both normal, then the components
or integrated circuit is damaged, the electric control
board should be replaced.
F7 7 light
coil pipe temp.
sensor of outdoor
unit fault
1、Check whether the resistance of sensor is normal,
otherwise replace it.
2、Check whether the sensor wire is short circuit or open
circuit, and whether the plug is well contacted, whether
there is welding off or rosin joint on the electric control
board, repair it if there is any above.
3、When the 1 and 2 are both normal, then the components
or integrated circuit is damaged, the electric control
board should be replaced.
F8 8 亮 light
suction temp.
sensor of
compressor fault
1、Check whether the resistance of sensor is normal,
otherwise replace it.
2、Check whether the sensor wire is short circuit or open
circuit, and whether the plug is well contacted, whether
there is welding off or rosin joint on the electric control
board, repair it if there is any above.
3、When the 1 and 2 are both normal, then the components
or integrated circuit is damaged, the electric control
board should be replaced.
F9 9 light
discharge temp.
sensor of
compressor fault
1、 Check whether the resistance of sensor is normal,
otherwise replace it.
2、Check whether the sensor wire is short circuit or open
circuit, and whether the plug is well contacted, whether
there is welding off or rosin joint on the electric control
Содержание
Похожие устройства
- Chigo CS/CU-25H3A-V84 Каталог Chigo 2011
- Chigo CS/CU-61H3A-P84 Инструкция по эксплуатации
- Chigo CS/CU-61H3A-P84 Сертификат
- Chigo CS/CU-61H3A-P84 Коды ошибок
- Chigo CS/CU-61H3A-P84 Каталог Chigo 2011
- Chigo CS/CU-21H3A-V84 Инструкция по эксплуатации
- Chigo CS/CU-21H3A-V84 Сертификат
- Chigo CS/CU-21H3A-V84 Коды ошибок
- Chigo CS/CU-21H3A-V84 Каталог Chigo 2011
- Rix I/O-W12S Инструкция по эксплуатации
- Rix I/O-W12S Инструкция по монтажу
- Rix I/O-W18S Инструкция по эксплуатации
- Chigo CS/CU-51H3A-P84 Инструкция по эксплуатации
- Chigo CS/CU-51H3A-P84 Сертификат
- Chigo CS/CU-51H3A-P84 Коды ошибок
- Chigo CS/CU-51H3A-P84 Каталог Chigo 2011
- Rix I/O-W09S Инструкция по эксплуатации
- Rix I/O-W09S Инструкция по монтажу
- Chigo CS/CU-32H3A-V84 Инструкция по эксплуатации
- Chigo CS/CU-32H3A-V84 Сертификат
Скачать
Случайные обсуждения